LC-502P/LC-508P

Quick S

tart Guide

5.4

Wiring Multiple Panels Together

As many as 24 floors may be controlled using a combination of LC-502Ps and LC-508Ps; the first
eight floors must be controlled by an LC-508P. After that, any combination of LC-502Ps and LC-
508Ps can be added to meet your floor requirements.

5.4.1

LC-508P/LC-502P Combination

Perform the following wiring instructions to accommodate an elevator application using an LC-
508P and one or more LC-502P panels (9 to 16 floors).

1. Make a complete set of connections to the LC-508P panel. Refer to Section 5.3 on page 15 and

Figure 10 on page 16 for all connections to the LC-508P.

2. Daisy-chain the Antenna and Ground reader connections from the LC-508P panel to the LC-

502P panel(s). Make the connections per the information in Table 5 and Figure 11 on page 18.

3. Daisy-chain the TxRx+, TxRx-, and Shield Network Communication connections from the

terminal strip on the LC-508P to each of the LC-502P panels. Make the connections per the
information in Table 6 and Figure 12 on page 19.

4. Refer to Section 5.2.1 on page 10 for the LC-502P floor relay connections.
5. Refer to Section 5.2.4 on page 15 for the LC-502P panel power connections.

Table 5: LC-508P to LC-502P

W-TB-B (Out)

W-TB-C (In)

LC-508P Reader Terminal Strip

LC-502P TB-5 or TB-6

Pin 2

Reader Antenna

Pin 1

Pin 1

Reader Ground

Pin 4

Table 6: LC-508P to LC-502P Panel Network

Communication Wiring

W-TB-B (Out)

W-TB-C (In)

Connection

LC-502P TB-1

Pin 4

TxRx-

Pin 1

Pin 5

TxRx+

Pin 2

Pin 6

Shield

Pin 3