4 common vent test — boilers – LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 11

Advertising
background image

Mighty Therm

2

Page 11

Personal injury or DEATH may occur. Natural

snowfall, drifting, and banking should all be taken

into account when locating the terminals in a

potential snow environment.

4. If the Mighty Therm2 is side-wall vented to the

same wall, locate the vent terminal at least 3

feet (0.9m) horizontally from the combustion air

terminal, and locate the vent terminal at least 1

foot (0.3m) above the combustion air terminal (

see

Figure 4

).

2.3.3 Vertical Vent Terminal

When the unit is vented through the roof, the

vent must extend at least 3 feet (0.9m) above the point

at which it penetrates the roof. It must extend at least

2 feet (0.6m) higher than any portion of a building

within a horizontal distance of 10 feet (3.0m), and high

enough above the roof line to prevent blockage from

snow. When the combustion air is taken from the roof,

the combustion air must terminate at least 12" (30cm)

below the vent terminal (

see Figure 3

). Seek local

municipalities and their codes for appropriate installation

techniques.

From Massachusetts Rules and Regulations 248 CMR 5.08:

(a) For all side wall horizontally vented gas fueled equip-

ment installed in every dwelling, building or structure

used in whole or inpart for residential purposes, includ-

ing those owned or operated by the Commonwealth and

where the side wall exhaust vent termination is less than

seven (7) feet above finished grade in the area of the

venting, including but not limited to decks and porches,

the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter shall

observe that a hard-wired carbon monoxide detector with

an alarm and battery back-up is installed on the floor level

where the gas equipment is to be installed. In addition, the

installing plumber or gasfitter shall observe that a battery op-

erated or hard-wired carbon monoxide detector with an alarm

is installed on each additional level of the dwelling, building

or structure served by the side wall horizontal vented gas

fueled equipment. It shall be the responsibility of the property

owner to secure the services of qualified licensed profes-

sionals for the installation of hard-wired carbon monoxide

detectors.

a. In the event that the side wall horizontally vented gas

fueled equipment is installed in a crawl space or an attic, the

hard-wired carbon monoxide detector with alarm and battery

back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision

cannot be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply with

the above requirements; provided, however, that during said

thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each

carbon monoxide detector as required in accordance with the

above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be

permanently mounted to the exterior of the building at a

minimum height of eight (8) feet above grade directly in line

with the exhaust vent terminal for the horizontally vented

gas fueled heating appliance or equipment. The sign shall

read, in print size no less than one-half (½) inch in size,

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4. INSPECTION. The state or local gas inspector of the side

wall horizontally vented gas fueled equipment shall not ap-

prove the installation unless, upon inspection, the inspector

observes carbon monoxide detectors and signage installed

in accordance with the provisions of 248 CMR 5.08(2)(a) 1

through 4.

(b) EXEMPTIONS: The following equipment is exempt from

248 CMR 5.08(2)(a) 1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not

Required To Be Vented" in the most current edition of NFPA

54 as adopted by the Board; and

2. Product Approved side wall horizontal vented gas fueled

equipment installed in a room or structure separate from the

dwelling, building or structure used in whole or in part for

residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT

VENTING SYSTEM PROVIDED. When the manufacturer of

Product Approved side wall horizontally vented gas equip-

ment provides a venting system design or venting system

components with the equipment, the instructions provided

by the manufacturer for installation of the equipment and the

venting system shall include:

1. Detailed instructions for the installation of the venting system

design or the venting system components; and

2. A complete parts list for the venting system design or venting

system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT

VENTING SYSTEMNOT PROVIDED. When the manufac-

turer of a Product Approved side wall horizontally vented gas

fueled equipment does not provide the parts for venting the

fuel gases, but identifies "special venting systems", the fol-

lowing requirements shall be satisfied by the manufacturer:

1. The identification of each "special venting system" shall

include either the listing of the website, phone number or

manufacturer's address where the venting system installation

instructions can be obtained; and

2. The "special venting systems" shall be Product Approved

by the Board, and the instructions provided with that system

shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for the Product

Approved side wall horizontally vented gas fueled equip-

ment, and all the venting instructions, parts lists, and/or

design instructions for the venting system shall remain

with the appliance or equipment at the completion of the

installation.

Manufacturers' websites where venting system installation

instructions may be obtained is located on the Laars website

at:

http://www.Laars.com.

2.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must be

used to prevent entry of rain water (

see Figure 3

). The

opening on the end of the terminal must be at least 12"

(30cm) above the point at which it penetrates the roof,

and high enough above the roof line to prevent blockage

from snow. When the vent terminates on the roof, the

combustion air must terminate at least 12" (30cm) below

the vent terminal.

2.4 Common Vent Test — Boilers

When an existing boiler is removed from a

common venting system, the common venting system is

likely to be too large for proper venting of the appliances

Advertising
This manual is related to the following products: