LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 9

Advertising
background image

Mighty Therm

2

Page 9

enclosed spaces containing combustion appliances.

Mighty Therm2 units are not allowed to be vented

into a common horizontal vent system, unless a properly

sized vent fan is used, and the common vent system is

properly designed by the vent fan manufacturer or a

qualified engineer.

Refer to the installation and operating instructions

on all appliances to be common vented for instructions,

warnings, restrictions and safety requirements. If safe

operation of all appliances connected to a common vent

cannot be assured, including prevention of spillage of

flue gasses into living spaces, common venting should

not be applied, and appliances should each be vented

separately.

2.2.4 Category III Vent

When the Mighty Therm2 is vented with horizontal

discharge, it must be installed per this installation

manual and the venting system manufacturer’s

installation instructions. The vent system must be sealed

stainless steel (

see Table 5

).

Route the vent pipe to the heater as directly as

possible. Seal all joints and provide adequate hangers

as required in the venting system manufacturer’s Instal-

lation Instructions. Horizontal portions of the venting

system must be supported to prevent sagging and may

not have any low sections that could trap condensate.

The unit must not support the weight of the vent pipe.

Horizontal runs must slope downwards not less than ¼

inch per foot (2 cm/m) from the unit to the vent terminal.

Reference

Table 2

for the size of the Category III vent

system. Up to three elbows can be used with 50 linear

feet (15.2m) of pipe. Subtract 10 allowable linear feet

(3.0m) for every additional elbow used.

WARNING

The outdoor vent terminal gets hot. Unit must be

installed in such a way as to reduce the risk of burns

from contact with the vent terminal.

2.3 Locating Vent & Combustion Air

Terminals

2.3.1 Side Wall Vent Terminal

The appropriate Laars side wall vent hood must

be used, and is listed in the installation and operation

manual. The terminal provides a means of installing

the vent piping through the building wall, and must

be located in accordance with ANSI Z223.1/NFPA 54

and applicable local codes. In Canada, the installation

must be in accordance with CSA B149.1 or .2 and local

applicable codes. Consider the following when installing

the terminal:

1.

Figure 4

shows the requirements for mechanical

vent terminal clearances for the U.S. and Canada.

2. Vent terminals for condensing appliances or

appliances with condensing vents are not permitted

to terminate above a public walkway, or over an

area where condensate or vapor could create a

nuisance or hazard.

3. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows, gravity

inlets or other openings. When possible, locations

under windows or near doors should be avoided.

5. Locate the vent terminal so that it cannot be

blocked by snow. The National Fuel gas code

requires that it be at a minimum of 12" above

grade. In a location that has the possibility of snow

accumulation, it is critical the installer places the

vent at least 12" higher than the maximum potential

snow line. Seek local municipalities and their codes

for appropriate installation techniques.

6. Locate the terminal so the vent exhaust does not

settle on building surfaces or other nearby objects.

Vent products may damage such surfaces or

objects.

7. If the boiler or water heater uses ducted combustion

air from an intake terminal located on the same

wall, locate the vent terminal at least 3 feet (0.9m)

horizontally from the combustion air terminal, and

locate the vent terminal at least 1 foot (0.3m) above

the combustion air terminal.

2.3.2 Side Wall Combustion Air Terminal

The Laars side wall combustion air terminal (see

Table 2

) must be used when the unit takes its combustion

air through a duct from a side wall. Consider the

following when installing the terminal:

1. Do not locate the air inlet terminal near a source

of corrosive chemical fumes (e.g., cleaning fluid,

chlorinated compounds, etc.)

2. Locate the terminal so that it will not be subject to

damage by accident or vandalism.

3. Locate the combustion air terminal so that it

cannot be blocked by snow. The National Fuel

gas code requires that it be at a minimum of 12"

above grade. Depending on local conditions, the

installer should ensure that it remains at least 12"

above the maximum potential snow line. Seek

local municipalities and their codes for appropriate

installation techniques.

WARNING: It is critical that the combustion

air intake and the vent terminals remain at least

12" above the maximum potential snow line.

If either the vent terminal or the air terminal is

blocked by snow, there may be potential for the

unit to produce excess carbon monoxide and or

recirculate flue gasses into the building/dwelling.

TERM

DESCRIPTION

Pipe

Must comply with UL Standard 1738

such as Type 29-4C Stainless Steel

(either insulated or non-insulated).

Joint

Follow vent manufacturer’s instructions

Sealing

Table 5. Required Horizontal Venting Material.

Advertising
This manual is related to the following products: