LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 29

Advertising
background image

Mighty Therm

2

Page 29

This step to be performed by a qualified service

person.

6.8 To Restart the Mighty Therm2

If drained, follow

Section 6.2

in this manual for

proper filling and purging.

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. WAIT FIVE (5) MINUTES.

4. Set the aquastat or thermostat to its lowest setting.

5. Open all manual gas valves.

6. Reset all safety switches (pressure switch, manual

reset high limit, etc.).

7. Set the temperature controller to the desired

temperature setting and switch on electrical power.

8. Burner will go through a prepurge period and

ignitor warm-up period, followed by ignition.

SECTION 7.

Maintenance

7.1 System Maintenance

1. Lubricate the system water-circulating pump, if

required, per the instructions on the pump.

2. If a strainer is employed in a pressure reducing

valve or the piping, clean it every six months.

3. Inspect the venting system for obstruction or

leakage at least once a year. Periodically clean the

screens in the vent terminal and combustion air

terminal (when used).

4. Keep the appliance area clear and free from

combustible materials, gasoline, and other

flammable vapors and liquids.

5. If the appliance is not going to be used for

extended periods in locations where freezing

normally occurs, it should be isolated from the

system and completely drained of all water. All

systems connected to it should also be drained or

protected from freezing.

6. Low water cutoffs, if installed, should be checked

every 6 months. Float type low water cutoff should

be flushed periodically.

7. Inspect flue passages, and clean with brushes/

vacuums, if necessary. Sooting in flue passages

indicates improper combustion. Determine the

cause and correct.

8. Inspect the vent system and air intake system,

and if the vent system is Category III, ensure that

all joints are sealed properly. If joints need to

be resealed, completely remove existing sealing

material, and clean with alcohol. Apply new sealing

material, and re-assemble.

7.2 Appliance Maintenance and Component

Description

No orifice changes are required to adjust the

Mighty Therm2 appliances for high altitude. High

altitude adjustment is accomplished by adjustment of the

gas valve manifold pressure and the air shutter(s). The

required instruments used to assist in these adjustments

are a CO

2

or O

2

Analyzer and a U-Tube Manometer or

other device capable of reading a pressure of 2.5-3.0

inches W.C. (0.62-0.75 kPa).

Start the adjustment process by checking the CO

2

in the “as installed” condition. Adjust the air shutter(s)

so that the CO

2

is about 8% or the O

2

is about 6.8% for

appliances operating on Natural Gas. For appliances

operating on LP Gas adjust the air shutter(s) so that the

CO

2

is about 9.2% or the O

2

is about 6.8%. Appliances

with two blowers should be adjusted so that the air

shutters below each blower are open the same amount.

Once the CO

2

or O

2

has been set, the manifold

pressure may be adjusted. Remove the 1/8 NPT plug

from the lower side of the gas valve that is to be set and

install a fitting, hose and manometer. Start the appliance

and observe the manifold pressure. Manifold pressure

must be adjusted to 3.0 in. W.C. (0.75 kPa) (for high

altitude only, standard operating pressure is 2.5 in. W.C.

(0.62 kPa)). It is adjusted by removing the slotted cap on

the gas valve and turning the adjustment screw (beneath

the cap) clockwise to increase pressure and replaced

after the adjustments have been completed and the

fitting, hose and manometer have been removed and the

1/8" plug has been replaced. Repeat this process until all

gas valves have been set. Note: The pressure can be set

only when the appliance is operating and only when the

particular gas valve being adjusted is energized by a call

for heat from the staging control.

After all of the gas valve manifold pressures have

been set, the CO

2

or O

2

must be reset. CO

2

or O

2

will

have changed when the manifold pressure was adjusted.

Open the air shutter(s) to reduce the CO

2

or O

2

to the

values achieved previously.

The procedure is complete when all gas valves are

adjusted to a manifold pressure of 3.0 in. W.C. (0.75

kPa) and the CO

2

is adjusted to 8.0% for Natural Gas

appliances or 9.2% for LP appliances (to be checked

only at full fire). When using an O

2

analyzer, the correct

O

2

is 6.8% for both Natural Gas and LP appliances.

Caution

Should any odor of gas be detected, or if the gas

burner does not appear to be functioning in a normal

manner, close main shutoff valve, do not shut off

switch, and contact your heating contractor, gas

company, or factory representative.

6.7 Shutting Down the Mighty Therm2

1. Switch off the main electrical disconnect switch.

2. Close all manual gas valves.

3. If freezing is anticipated, drain the Mighty Therm2

and be sure to also protect building piping from

freezing.

Advertising
This manual is related to the following products: