LAARS Mighty Therm2 MT2V (Sizes 500–2000 MBTU/h) - Install and Operating Manual User Manual

Page 15

Advertising
background image

Mighty Therm

2

Page 15

The Mighty Therm2 can be used with several

different types of readily available storage tanks. A pump

draws water from the storage tank and pumps the water

through the heater and back into the tank. Pump-mount-

ed units have a circulating pump built into the water

heater. The pumps used are sized for the headloss

through the heater, plus 30 feet (9.1m) of full-sized pip-

ing (same size as boiler outlet) and a normal number of

fittings. Pumps used on pump-mounted unit are sized for

soft/normal or hard water, so make sure a pump-mounted

unit matches the water quality of the installation.

Pipe the outlet from the heater’s relief valve

such that any discharge from the relief valve will be

conducted to a suitable place for disposal when relief

occurs. Do not reduce line size or install any valves in

this line. The line must be installed to allow complete

drainage of both the valve and the line.

Suggested piping diagrams are shown in

Figures 11

through 14

. These diagrams are meant only as a guide.

Components required by local codes must be properly

installed.

The minimum inlet water temperature for the

Mighty Therm2 is 120°F (49°C) to avoid condensing on

the copper coils.

4B.2 Hot Water Supply Piping —

Water Heater

Follow the tank manufacturer’s guidelines for

completion of the hot water system connections.

NOTE: A listed temperature and pressure relief valve

listed as complying with the Standard for Relief

Valves and Automatic Gas Shutoff Devices for Hot

Water Supply Systems (ANSI Z21.22 / CSA 4.4) of

suitable discharge capacity must be installed in the

separate storage tank system.

If the Mighty Therm2 water heater is installed

in a closed water supply system, such as one having a

backflow preventer in the cold water supply line, the

relief valve may discharge periodically, due to thermal

expansion. Means (such as a properly-sized expansion

tank) shall be provided to control thermal expansion.

Contact the water supplier or local plumbing inspector

on how to control this situation.

4B.3 Water Flow Requirements —

Water Heater

In a water heating application (an open system),

new water is constantly being introduced. With the

new water comes a fresh supply of minerals that can

be deposited on the unit’s heat exchanger. This is

commonly known as scaling. The amount of minerals

will depend upon the hardness of the water. Water can

also be aggressive, and can erode metals, including

copper, if the water is moved too quickly. The water flow

requirements for the Mighty Therm2 water heater are

based upon the hardness of the water. The water flow

is kept high enough to prevent scaling, but low enough

to prevent tube erosion. For extremely soft or hard

water, cupro-nickel tubes are available. Contact a Laars

Representative if you have questions or concerns about

water quality.

Pump-mounted water heaters can be ordered

with standard pumps for soft or normal water or with

pumps for hard water. The pumps used are sized for the

headloss through the heater, plus 30 feet (9.1m) of full-

sized piping (same size as heater outlet) and a normal

number of fittings.

Table 9

specifies water flow rates for water heaters,

which will enable the user to size a pump. The headloss

shown is for the heater only, and the user will need to add

the headloss of the piping system to properly size the pump.

4B.4 Combined Water Heating (potable)

and Space Heating — Water Heater

NOTE: These systems are not allowed in the

Commonwealth of Massachusetts.

Piping and components connected to this water

heater for the space heating application shall be suitable

for use with potable water.

Toxic chemicals, such as used for boiler treatment,

shall not be introduced into the potable water used for

space heating.

This water heater when used to supply potable

water shall not be connected to any heating system or

component(s) previously used with a non-potable water

heating appliance.

When the system requires water for heating at

temperatures higher than required for other uses,

an anti-scald mixing or tempering valve shall be

installed to temper the water for those uses in order

to reduce scald hazard potential.

4B.5 Freeze Protection – Water Heater

Although Mighty Therm2 water heaters are design-

certified for outdoor installations, such installations

are not recommended in areas subject to freezing

temperatures, unless proper precautions are taken.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices, etc.,

may prevent a heater from firing. Any time a heater is

subjected to freezing conditions, and the heater is not

able to fire, and/or the water is not able to circulate,

there is a risk of freezing in the heater or in the pipes

in the system. When water freezes, it expands. This

can result in bursting of pipes in the system, or damage

to the heater, which could result in leaking or flooding

conditions.

Contact the local factory representative or Laars for

additional information.

SECTION 5.

Electrical Connections

Advertising
This manual is related to the following products: