Out of production – LAARS Horizon - Installation, Operation and Maintenance Instructions User Manual

Page 3

Advertising
background image

Horizon

Page 3

SECTION 1.

General Information

1A. Freight Claims

Inspection should be made of boiler and

components for damage upon arrival. Any claims for

damage should immediately be filed against the

carrier by the consignee.

1B. General Information

These boilers have been designed and

constructed according to the requirements of the

relevant ASME Codes using heavy gage steel plate

and boiler tubes. They are of the three pass horizontal

tube design using a reverse flame technique in the

boiler to impart a high heat transfer in the primary

heating zone before directing gases into the third pass.

The compact tubular third pass incorporates

special stainless steel flue gas baffles with extension

rods to allow full insertion of the baffles into the back

end of tubes where they are most effective.

A 5 gal/min. domestic hot water coil is located at

the top of the boiler in the hottest zone for ample hot

water supply. A unique feature of its attachment is the

raised coil flange which allows the use of clamping

bolts rather than studs, thereby eliminating water leaks

caused by broken studs.

Two ceraform lined doors provide easy access

for cleaning, the lower door with burner attached

remaining in position while the upper door is removed

for tube cleaning.

A flame observation port is provided for setting-

up burner and a test hole gives access for CO

2

and

draft readings.

The boiler is encased in a fully insulated baked

enamel jacket and comes completely pre-assembled

for easy installation. Alternatively, it can be supplied

in knock-down form.

Caution

This boiler is designed for use in closed systems
where air is eliminated from the system and no more
oxygen is allowed to enter (typical baseboard or
radiator system). Do not directly connect this boiler
to a system utilizing rubber or plastic tubing which
has an oxygen permeation rating greater than 0.1
milligrams / liter / day. Damage to the boiler will
result and the warranty will be void (see warranty
section 4g).

1C. Boiler Installation

For recommended installation practice reference

should be made to the National Fire Protection

Standard for Oil Burning Equipment - NFPA 31 -

Latest Edition.

1D. Boiler Location

The boiler should be positioned as near to the

chimney as possible and have a minimum smoke-pipe

connector length of 18".

1E. Boiler Clearances (minimum)

Top - 6"; Front - 24"; Rear - 6"; Sides - 6".

1F. Floor

The boiler must be mounted on a non-

combustible masonry or cement floor with no

combustibles underneath.

1G. Combustion and Ventilation Air

To insure an adequate supply of fresh air for

combustion and ventilation an inlet and outlet opening

should be provided at floor and ceiling level. Each

opening must have a minimum of one square inch of

free area for every 1000 BTU/h of input or 140 square

inches per gallon of oil burned per hour. The openings

must not be in a position liable to blockage.

1H. Chimney and Draft Requirements

To assure the safe and proper operation of the oil

burner the boiler must be connected to a chimney

having sufficient draft at all times to evacuate the flue

gases to atmosphere. A draft regulator should be

installed in the smoke-pipe as near to the flue as

possible and adjusted to achieve an over fire draft of

0.01 in. W.C.

1I. Jacket (normally fitted)

If not fitted, assemble panels in accordance with

instructions in Figure 2.

1J. Oil Burner (normally fitted)

If not fitted, insert burner tube into boiler so that

it is recessed approximately 1/4" back from the inside

wall of door insulation, then clamp mounting flange

and bolt up to front-plate.

The burner should be wired and connected to the

oil line in accordance with the manufacturer’s

instructions.

1K. Boiler Controls (normally fitted)

If controls are supplied separately, fit them to the

boiler in the positions shown in Figure 2, with jacket

in place.

Circulator - 1 1/4' return tapping at rear of boiler.

Tridicator - temp./press. gauge - 1/2" tapping at

top of boiler.

Relief Valve - 3/4" tapping at top of boiler. Pipe

to safe place of discharge.

Aquastat Relief - L8124A - 3/4" tapping.

Fit a drain valve (not supplied) in the hydronic

return tee. Check that all connections are made water

tight.

OUT OF

PRODUCTION

Advertising