• The Offset setting does not change the ratio selection. For instance, with 1.00 (OD):1.00

(SYS) Reset Ratio, the System water temperature (SYS) will always increase one degree

for each degree change in the Outdoor temperature (OD). What the Offset does is add or

subtract a constant temperature value. See "Outdoor Reset Concept" on page 7.

• If required: Adjust the Water Offset in mild weather. If the ambient building

temperatures are too warm in mild weather, decrease the offset. If the ambient building

temperatures are too cold in mild weather, increase the Water Offset. The rule of thumb

for baseboard radiation is to change the offset 4°F for every 1°F you wish to change the

building temperature. In radiant heat applications, change the offset 1°F or 2°F for every

1°F you wish to change the building temperature.

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater

Temperature (in °F)

Custom Reset Ratio

Point1: System=120°F

Oudoor=60°F

Point2: System=170°F

Oudoor=0°F

Point1

Point2

Customized Reset Ratio

Max Target

Min Target

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater

Temperature (in °F)

Target Offset

Offset=10°F

Reset Ratio=1.5 : 1.0

Reset Ratio

Max Target

Min Target

Reset Ratio + 10F Offset

Min Target=120°F

Max Target=170°F

OUTdOOR CUTOFF TEMPERATURE

Adjustable: Off, from 20ºF / 70ºC - 100ºF / 38ºC, On

Default: 65ºF/ 18ºC

Button: MENU/Set Point/Offset/Outdoor Cutoff

• The Outdoor Cutoff screen will automatically appear after the offset has been selected.

• When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the

M4-CNC will control and modulate boilers to hold the calculated temperature.

- OUTDOOR CUTOFF -

65

o

F

[

]

BACK ▲ ▼ SAVE

• When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the M4-CNC will turn all boilers off. The System

relay will remain energized for the Run-On delay then de-energize.

• The Outdoor Cutoff can be set from 20°F to 100°F. In addition, it can be set to ON or OFF. In the ON position, the System Relay

will run regardless of the Outdoor temperature (OD) and the burner stages will be active to hold the calculated water temperature.

(Note: The lowest water temperature the M4-CNC will circulate is 70°F. If the Outdoor Cutoff is turned ON and the Season is set

to Winter, the M4-CNC will circulate at least 70°F water even in the hottest of weather.) In the OFF position, the system pump will

always be off and all burner stages will be off.

MiNiMUM WATER TEMP

Adjustable from 70ºF/21ºC to 180ºF/82ºC

Default: 70ºF/ 21ºC

Button: MENU/Set Point/Offset/Outdoor Cutoff/Minimum Water Temp

• The Minimum Water Temperature must be set to the boiler manufacturer’s specification.

The M4-CNC will calculate the Set Point based on the Outdoor temperature (OD), the Reset

Ratio, and the Offset value. The M4-CNC will control all boilers to hold either the Set Point

temperature, or the Minimum Water Temperature, whichever is higher.

• The Minimum Water Temperature must be at least 20°F lower than the Maximum

Temperature (See next setting).

MINIMUM WATER TEMP

70

o

F

[ ]

BACK ▲ ▼ SAVE

MAxiMUM WATER TEMP

Adjustable 90ºF/21ºC - 240ºF/116ºC

Default: 240ºF/116ºC

Button: MENU/Set Point/Offset/..../Maximum Water Temperature

• This is the highest temperature heating water the M4-CNC will circulate through the heating

system.

• When using a radiation system, it should be set according to the tubing or floor

manufacturer’s specification.

• The Maximum Temperature must be at least 20°F higher than the Minimum Temperature

(See previous setting).

• The Maximum Temperature must be set lower than the boilers high limit for correct system

temperature control.

MAXIMUM WATER TEMP

240

o

F

[

]

BACK ▲ ▼ SAVE

LAARS Modulating Controls M4 & M4-EXT