OUTdOOR RESET CONCEPT

The M4-CNC has multiple operating modes that satisfy most hydronic systems. It changes

the System Set Point based on outdoor temperature (Outdoor Reset). The M4-CNC varies the

temperature of the circulating heating water in response to changes in the outdoor temperature.

The heating water temperature is controlled through the modulation or sequencing of the

stages.

The M4-CNC also controls the system circulating pump with an adjustable Outdoor Cutoff.

When the outdoor temperature is above the Outdoor Cutoff, the pump is off and no heating

water is circulated through the system. When the outdoor temperature drops below the

Outdoor Cutoff, the system pump relay is activated and the heating water circulates through

the system. The temperature of the heating water is controlled by the Reset Ratio, Water

Offset, and changes with Outdoor temperature.

RESET RATiO/OUTdOOR RESET

When a building is being heated, heat escapes through the walls, doors, and windows to

the colder outside air. The colder the outside temperature, the more heat escapes. If you

can input heat into the building at the same rate that it is lost out of the building, then the

building temperatures will remain constant. The Reset Ratio is an adjustment that

lets you achieve this equilibrium between heat input and heat loss.

The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor

Temperature : Heating Water Temperature) ratio. This means that for every

degree the outdoor temperature drops, the temperature of the heating water will

increase one degree. The starting point of the curve is adjustable, but comes

factory selected at 70

°

F Outdoor Temp. and 100

°

F Water Temp. For example with

a 1.00 (OD):1.00 (SYS) ratio, if the outdoor temperature is 50

°

F, this means the

temperature has fallen 20

°

from the starting point of 70

°

F. Therefore, the heating

water temperature will increase 20

°

to 120

°

F.

Each building has different heat loss characteristics. A very well insulated

building will not lose much heat to the outside air, and may need a Reset Ratio

of 2.00 (OD):1.00 (SYS) (Outdoor:Water). This means the outdoor temperature

would have to drop 2 degrees to increase the water temperature 1 degree. On

the other hand, a poorly insulated building with insufficient radiation may need

a Reset Ratio of 1.00 (OD):2.00 (SYS). This means that for each degree the

outdoor temperature dropped the water temperature will increase 2 degrees.

The M4-CNC has a full range of Reset Ratios to match any buildings heat loss

characteristics.

A heating curve that relies not only on Outdoor temperature but also on the type of

radiation will improve heat comfort. The following are suggested initial settings

for different types of radiation based on average building insulation and heat loss.

The contractor can fine tune these adjustments based on the specific building need.

Type of Radiation in Building

Reset Ratio

Offset

Radiators (Steel & Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Baseboard (Finned copper tube& Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Radiant (High Mass/Concrete)

4.00 (OD) : 1.00 (SYS)

-10˚F

Radiant (Low Mass/Joists)

2.00 (OD) : 1.00 (SYS)

-10˚F

Fan Coils & Air Handlers

1.00 (OD) : 1.00 (SYS)

20˚F

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

110

100

90

80

Outdoor Temperature

W

at

er

Te

m

pe

ra

tu

re

70

40

50

60

150

140

130

120

1:4

With a 0° Offset, the
Reset curves begin at
100° Water Temperature.

With a -20° Offset, the
Reset curves begin at
80° Water Temperature.

With a +20° Offset, the
Reset curves begin at
120° Water Temperature.

1:4

1:4

1:1

1:1

1:1

4:1

4:1

4:1

90

100

+20 Offset

-20 Offset

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

1:4

1:1

4:1

Colder

Warmer

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

100

120

110

130

140

150

160

180

170

190

200

210

220

1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1

4:1

W

ater

Temperature (in °F)

Reset Ratio Curves

Reset Ratio is Presented as

Outdoor Temp. : Water Temp. Ratio

1:4

LAARS Modulating Controls M4 & M4-EXT

HT# 059104-00 B