dAY / NigHT SCHEdULE

DAY/NIGHT SCHEDULE

Set Time

**:**

Day Schedule 6:00a

Night Schedule

8:00p

BACK ▲ ▼ SAVE

-- DAY SCHEDULE --

6:00 Am

BACK ▲ ▼ SAVE

dAY/NigHT SCHEdULES

(Available when "Shutdown or Tstat" is selected from the Shutdown/

Tstat/Setback Startup menu option only)

Button: MENU/<System Settings>/<More Settings>/Day/Night Schedule

• The M4-CNC has two levels of heat. The Day (Normal) level is used when a building is

occupied and people are active.

• The Night (Setback) level is used when a building is not occupied, or when people are

sleeping. This setting reduces the calculated temperature by the Setback setting. See

"Setback" on page 24. If the Day calculated water temperature was 150˚F and the Setback

was 20˚F, the Night Schedule will run at (150˚F - 20˚F) = 130˚F.

• If the Boost feature is being used, it uses the Day Schedule as the Boost ending point. See "Boost Mode" on page 20. That is, if the

Day Schedule is set to start at 6:00AM, the Boost will start 30 minutes prior to the Day setting at 5:30AM. The M4-CNC will then

raise the calculated water temperature by the Setback amount. Using the previous example, at 5:30AM the M4-CNC will raise the

calculated water to 170˚F = (150˚F + 20˚F) until 6:00AM.

SET TiME

Button: MENU/<System Settings>/<More Settings>/Set Time

• Adjust the time by selecting Set Time from the menu and then scrolling through the hours

then select Save. Then, scroll through the minutes then select Save. If the hours are to be

set to PM, scroll through the AM hours to reach the PM hours.

----- SET TIME -----

7:35 Pm

BACK ▲ ▼ SAVE

ALERT

Remember that the battery is the backup for the Time. If no power is supplied to the

M4-CNC and

there was no battery or the battery had no power, time values will be lost and will need to be reset.

HiSTORY

Button: MENU/<Histories>

The M4-CNC provides users with a graphical history of the System and Outdoor temperatures for

the previous 24 hours. The temperatures are sampled every 12 minutes. That is, readings of both

System and Outdoor temperatures are recorded and stored every 12 minutes for the last 24 hours.

• To view the values of specific time period, use the two middle buttons to scroll to that time

and read the upper left temperature.

• The first screen will be the System Temperature History. By clicking on the Next button,

you'll be able to view the Outdoor Temperature History.

----------- SETTINGS ------------

Season

Winter

Set Point

70 F

<System Settings>

<Maintenance>

<Histories>

<System Startup>

BACK

SELECT

BACK

SAVE

------------- SEASON --------------

Winter

Summer

BACK

SAVE

------------ SET POINT ----------

70

F

[

]

--------- RESET RATIO ----------

1.00 OD=4.00 Sys

1.00 OD=3.00 Sys

1.00 OD=2.00 Sys

1.00 OD=1.50 Sys

1.00 OD=1.25 Sys

1.00 OD=1.00 Sys

1.25 OD=1.00 Sys

1.50 OD=1.00 Sys

2.00 OD=1.00 Sys

3.00 OD=1.00 Sys

4.00 OD=1.00 Sys

BACK

SAVE

BACK

START

-------- SYSTEM STARTUP ------

(START)

to continue

BACK

CONTINUE

------------- WARNING ------------

THESE SETTINGS

CHANGE PRIMARY

SYSTEM FUNCTIONS.

-------- ARE YOU SURE? -------

No

Yes

---------- SENSOR TYPE ---------

Set Point F

Set Point C

Reset F

Reset C

----- SETBACK/SHUTDOWN -----

Shutdown/Disable

Tstat/Enable

Setback

STARTUP

Reset Ratio

Set Point

BACK

SAVE

------- OUTDOOR CUTOFF -------

65

F

[

]

-------------- OFFSET -------------

+0

F

[

]

BACK

SAVE

--- MINIMUM WATER TEMP ----

70

F

[

]

BACK

SAVE

--- MAXIMUM WATER TEMP ----

240

F

[

]

Reset Ratio

BACK

SAVE

Shutdown or TStat Input

Setback Input

HISTORIES

--- SYS= 91 F, 10:57Am ---

--- OD= 54 F, 11:36Am ---

------ EMS INPUT MODE -------

Disable

Enable

Reset Options

Set Point

----- EMS 4ma SETPOINT-----

120

F

[

]

------ EMS 20ma SETPOINT-----

220

F

[

]

---------- BOOST MODE ---------

30 Minutes

Disabled

BACK

SAVE

--------- SENSOR FAULT --------

All Off

All On

BACK

SAVE

------- OUTPUT D TYPE --------

4-20ma

0-10v

0-5v

2-10v

1-5v

BACK

SAVE

----- PROVE/DHW SHARING ----

Prove

DHW Priority

DHW No Priority

No Priority (Summer)

BACK

SAVE

------ MODULATION MODE ------

Normal

Parallel

BACK

SAVE

BACK

SAVE

BACK

SAVE

------- OUTPUT A TYPE --------

4-20ma

0-10v

0-5v

2-10v

1-5v

BACK

SAVE

BACK

SAVE

BACK

SAVE

BACK

EXIT

BACK

NEXT

BACK

SAVE

BACK

SAVE

Enabled

BACK

SAVE

------- DHW SETPOINT -------

180

F

[

]

Disabled

----------- SETTINGS ------------

Season

Winter

Set Point

70 F

<System Settings>

<Maintenance>

<Histories>

<System Startup>

BACK

SELECT

BACK

SAVE

------------- SEASON --------------

Winter

Summer

BACK

SAVE

------------ SET POINT ----------

70

F

[

]

--------- RESET RATIO ----------

1.00 OD=4.00 Sys

1.00 OD=3.00 Sys

1.00 OD=2.00 Sys

1.00 OD=1.50 Sys

1.00 OD=1.25 Sys

1.00 OD=1.00 Sys

1.25 OD=1.00 Sys

1.50 OD=1.00 Sys

2.00 OD=1.00 Sys

3.00 OD=1.00 Sys

4.00 OD=1.00 Sys

BACK

SAVE

BACK

START

-------- SYSTEM STARTUP ------

(START)

to continue

BACK

CONTINUE

------------- WARNING ------------

THESE SETTINGS

CHANGE PRIMARY

SYSTEM FUNCTIONS.

-------- ARE YOU SURE? -------

No

Yes

---------- SENSOR TYPE ---------

Set Point F

Set Point C

Reset F

Reset C

----- SETBACK/SHUTDOWN -----

Shutdown/Disable

Tstat/Enable

Setback

STARTUP

Reset Ratio

Set Point

BACK

SAVE

------- OUTDOOR CUTOFF -------

65

F

[

]

-------------- OFFSET -------------

+0

F

[

]

BACK

SAVE

--- MINIMUM WATER TEMP ----

70

F

[

]

BACK

SAVE

--- MAXIMUM WATER TEMP ----

240

F

[

]

Reset Ratio

BACK

SAVE

Shutdown or TStat Input

Setback Input

HISTORIES

--- SYS= 91 F, 10:57Am ---

--- OD= 54 F, 11:36Am ---

------ EMS INPUT MODE -------

Disable

Enable

Reset Options

Set Point

----- EMS 4ma SETPOINT-----

120

F

[

]

------ EMS 20ma SETPOINT-----

220

F

[

]

---------- BOOST MODE ---------

30 Minutes

Disabled

BACK

SAVE

--------- SENSOR FAULT --------

All Off

All On

BACK

SAVE

------- OUTPUT D TYPE --------

4-20ma

0-10v

0-5v

2-10v

1-5v

BACK

SAVE

----- PROVE/DHW SHARING ----

Prove

DHW Priority

DHW No Priority

No Priority (Summer)

BACK

SAVE

------ MODULATION MODE ------

Normal

Parallel

BACK

SAVE

BACK

SAVE

BACK

SAVE

------- OUTPUT A TYPE --------

4-20ma

0-10v

0-5v

2-10v

1-5v

BACK

SAVE

BACK

SAVE

BACK

SAVE

BACK

EXIT

BACK

NEXT

BACK

SAVE

BACK

SAVE

Enabled

BACK

SAVE

------- DHW SETPOINT -------

180

F

[

]

Disabled

MAiNTENANCE

Button: MENU/<Maintenance>

The Maintenance menu gives access to sensor and outputs trimming. In addition, you'll have

access to view the Startup configuration settings.

ALERT

To be able to change the

M4-CNC settings the Program/Run Switch must be set

to Program. The switch is located under the Enclosure Wiring Cover for security.

The Enclosure Wiring Cover can be securely closed using a lock.

----- MAINTENANCE ----

System Trim

+0

o

F

Outdoor Trim

0

o

F

<Output Trim>

<Configuration>

BACK ▲ ▼ SAVE

SYSTEM

A
B
C
D

Full Modulation Sequencing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 12VA MAX

INPUT RATINGS:

USE COPPER CONDUCTORS ONLY

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA