2G. Water System Requirements

2G-1. Flow Requirements

The Model HH boilers must have continuous

flow through the heat exchanger when firing for
proper operation. The system pump must be capable
of developing sufficient pressure to overcome the
resistance of the boiler plus the entire circulating
system at the designated flow (see Table 5). The
temperature rise across the boiler should never exceed
40°F (22°C).

2G-2. Variable Water Flow Systems

There can be reduced water flow through the

boiler in heating systems using zone valves, zone
pumps or 3-way valves. This can result in a high
temperature rise across the boiler. Laars recommends
primary-secondary pumping for all variable flow
systems. The boiler pump in a primary-secondary
system maintains constant flow through the boiler
even though the system flow is variable. In a primary-
secondary system the pressure drop of the boiler is not
added to the system (see Figure 5).

NOTES: Sizes 320M and 400M use 4-pass heat exchangers; 520M, 625M and 775M use 2-pass heat exchangers.
*Pressure drop (head loss) through the boiler, expressed in ft. of H

2

O.

Shaded area is the recommended flow and temperature rise. Minimum inlet temperature is 105°F.

Table 5. Temperature Rise.

TEMPERATURE RISE IN DEGREES (°F / °C )

MODEL

10°F

6°C

15°F

8°C

20°F

11°C

GPM

H/L ft.

LPS

H/L m

GPM

H/L ft.

LPS

H/L m

GPM

H/L ft.

LPS

H/L m

HH0320M
HH0400M
HH0520M
HH0625M
HH0775M
HH1000M

54
68
88

106
132
170

11.2
26.2

8.9

12.2
22.5
37.3

3.41
4.29
5.55
6.69
8.33

10.73

3.4
8.0
2.7
3.7
6.9

11.4

36
45
58
70
87

113

5.0

11.5

4.0
5.7
9.4

16.5

2.27
2.84
3.66
4.42
5.49
7.13

1.5
3.5
1.2
1.7
2.9
5.0

27
34
44
53
65
85

2.8
6.6
2.6
3.3
5.2
9.4

1.70
2.15
2.78
3.34
4.10
5.36

0.9
2.0
0.8
1.0
1.6
2.9

Flow

High

Normal

Low

Figure 5. Primary-Secondary Plumbing.

Boiler Circulation

Pump

Cold Water

Make-Up

System Pump

12"

Max.

12"

Max.

12"

Max.

12"

Max.

Thermometer

Temperature
Sensor

Globe Valve

Check Valve

Pressure Reducing Valve
w/Fast Fill Bypass

Expansion Tank
with Air Scoop and
Auto Air Vent

3-Way Valve

Valve

Pump

LEGEND:

Boiler circuit piping must be equal to or larger than
boiler water connection size.

Boiler circulation pump sized for flow through
boiler.

Dotted devices indicate alternate locations.

WARNING: This drawing shows suggested
piping configuraiton and valving. Check with
local codes and ordinances for additional
requirements.