LAARS Mighty Max HH (Sizes 320M - 1000M) - Installation, Operation and Maintenance Instructions User Manual

Page 20

Advertising
background image

Page 20

LAARS HEATING SYSTEMS

Caution

This appliance is equipped with an ignition
device which automatically lights the burner.
Do not try to light the burner by hand.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any
phone in your building.

Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.

If you don't smell gas, go to the next step.
7.

Turn on manual gas valves.

8.

Rest all safety devices (manual resets on high
limit, low water cutoff, etc.).

9.

Replace control access panel.

10.

Turn on all electric power to the boiler.

11.

Set thermostat to desired setting.

12.

If the boiler will not operate, follow the
instructions to turn off gas to boiler and call your
service technician or gas supplier.
a.

Turn off main electrical switch.

b.

Close all manual gas valves.

3D-1. Setting Temperature Controls

The temperature control differential is factory

set at 15°F. This setting can be adjusted from 1 to
30°F to suit your application. Adjustment is made by
taking the cover off the temperature controller and
turning the potentiometer marked “DIFF”, which is
located just below and to the left of the controller’s
setpoint dial.

To set the temperature and high-limit controls:

a.

Set the temperature controller at the system
design temperature.

b.

For boilers with the temperature controller bulb
at the boiler inlet, set the high-limit 40°F to 50°F
above temperature controller setting.

c.

For boilers with the temperature controller bulb
at the boiler outlet, set the high-limit 15°F to
25°F above temperature controller setting.

3E. To Shut Down System

To shut down the boiler, turn off all manual gas

valves and electrical disconnect switch.

NOTE: There is a filter which needs to be cleaned
prior to setting pressures. See Section 4D-2 “Filter
Service” before proceeding.

3F. Venturi Combustion Flow System

Verifying proper operation of the combustion

flow system has two aspects - air flow and gas flow.
Air flow is checked by measuring pressures at service

taps on the venturi. Gas flow is checked by evaluating
venturi pressures and the regulator offset pressure.

In a venturi flow system the difference between

various pressures is far more important than their
“gauge” value relative to the room. The gas pressure
offset and the gas orifice pressure differential are
especially important concepts. The following section
describes this setup procedure.

3F-1. Pressure Measurement Ports

Air flow enters the venturi through the filter box

and blower assembly. It is pushed through a
converging section and into the throat, where pressure
is reduced substantially. Gas flow is pulled into the
throat through an orifice. The orifice is located
between the throat and the regulator. Air and gas are
combined in the throat and mix thoroughly as they
proceed through the venturi tailpipe to the burner.

Service taps are provided at three places. One is

located on the chamber with the gas connection, this
tap is called the gas plenum tap. The other is located
above the gas plenum tap, this port is called the
venturi inlet tap. The third tap, gas orifice tap, is
located on the red orifice holder directly before the
gas connects to the venturi. These taps have service
plugs in them. Do not remove any of the plastic
fittings or plastic tubing. To evaluate system operation
requires accurate measurement at these taps. An
inclined manometer with a zero to 6 inches water
column range is ideal. Other instruments may be used,
but the “positive/negative” nature of the readings must
be well understood. Gas pressure offset measurements
are at very low levels (0.4" WC), the instrumentation
must be capable of determining it accurately.

3F-2. Venturi Adjustment

Note that an equalizer tube is connected from a

port on the side of the venturi inlet to the port of the
regulator. This is a very important component which
allows the regulator to track air pressure even when
abnormal conditions occur, such as blockage of the
combustion air. Before firing, confirm that this tube
and the venturi pressure switch tubes are in place and
firmly connected.

The field checkout involves measuring gas and

venturi pressures, and observing the flame through the
sight glass. If necessary, the gas input rate can be
measured by timing the gas meter.

Install shutoff valves at the gas orifice (regulator

outlet) tap (red), at the venturi inlet tap and at the gas
plenum tap. Do not remove any of the plastic fittings
or plastic tubing. After installing the shutoff valves,
be certain they are closed.

a. Unfired Venturi Differential Pressure

NOTE: Turn off the main manual gas valve.

Advertising