Table 19 — Test of Output Signals

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS/ACTION

OUTPUTS

Field testing of outputs. (Set HOA switch to OFF.)

HCV %

Press ENTR if unit is equipped with a hot water or steam valve. Otherwise press

HCV TEST

Verify that the hot water or steam valve strokes to its 100% position.

CCV %

The hot water or steam valve returns to its 0% position. Press ENTR if unit is equipped with a chilled water

valve. Otherwise press

CCV TEST

Verify that the chilled water valve strokes to its 100% position.

MIXD %

The chilled water valve returns to its 0% position. Press ENTR if unit is equipped with mixed-air dampers.

Otherwise press

MIXD TEST

Verify that the outdoor-air damper strokes to its 100% position. Proceed with the applicable Constant Volume
or Variable Air Volume portion of the test.

For Constant Volume Units:

IGV %

If so equipped, verify that the outdoor-air damper returns to its 0% position. (Set the HOA switch
to AUTO.)

SF X

FAN TEST

Supply fan will be turned ON automatically. If unit is equipped with the Option Module, proceed with the
Option Output portion of the test (Table 20). If the unit does not have an Option Module, proceed to the electric
heater portion of the test (Table 21). If unit does not have an Option Module or electric heater, proceed as
follows:

EXIT TST

TST CMPL

Test is now complete. The unit is back under normal automatic control.

For Variable Air Volume Units:

IGV %

If so equipped, verify that the outdoor-air damper returns to its 0% position.

IGV TEST

Verify that the IGVs stroke to their 100% position. Close the door of the fan section. Turn the HOA switch
to AUTO.

SF X

The IGVs return to their 0% position.

FAN TEST

The supply fan is turned ON automatically.

HIR X

The supply fan stops.

HIR TEST

Using an ohmmeter across the HIR relay contacts (refer to component arrangement label for location), the
reading should be less than 10 ohms. If the unit is equipped with the option module, proceed with the option
output portion of the test (Table 20). If unit does not have an option module, proceed to the electric heater
portion of the test (Table 21). If unit does not have an option module or electric heater, proceed as follows:

EXIT TST

TST CMPL

Test is now complete. The unit is back under normal automatic control.