Table 1 — input and output points – Carrier 39L User Manual

Page 12

Advertising
background image

Table 1 — Input and Output Points

MODULE,

DEFAULT ADDRESS

INPUT

INPUT

TYPE

CHANNEL

NUMBER

OUTPUT

OUTPUT

TYPE

CHANNEL

NUMBER

PSIO (Processor)
ADDRESS 1

SAT

AI

1

IGV*

AO

13

OAT

AI

2

MIXD

AO, DO†

14

MAT

AI

3

HWC

AO

15

RH

AI

4

CWC

AO

16

LTT

DI

5

SF

DO

17

SPT

AI

6

HIR*

DO

18

RAT

AI

7

—

—

—

SP*

AI

8

—

—

—

AFS

DI

9

—

—

—

FLTS

DI

10

—

—

—

OARH

AI

11

—

—

—

ENT

DI

12

—

—

—

PSIO (Option)
ADDRESS 31

SVP*

AI

31

RFVC*

AO

43

RVP*

AI

32

HUM1

AO, DO

44

DHH

DI

33

HUM2

DO

45

TEMP

AI

34

AOTC

AO

46

PRES

DI

35

DOTC

DO

47

EVAC

DI

36

DTCC

DO

48

PURG

DI

37

—

—

—

FSD

DI

38

—

—

—

AQ1

AI

39

—

—

—

AQ2

AI

40

—

—

—

OAVP*

AI

41

—

—

—

METER

DI

42

—

—

—

DSIO (Electric Heat)
ADDRESS 19

—

—

—

EHS1

DO

23

—

—

—

EHS2

DO

24

—

—

—

EHS3

DO

25

—

—

—

EHS4

DO

26

—

—

—

EHS5

DO

27

—

—

—

EHS6

DO

28

—

—

—

EHS7

DO

29

—

—

—

EHS8

DO

30

DSIO (DX without
Electric Heat)
ADDRESS 19

CUST

DI

19

DXS1

DO

23

DXSD

DI

20

DXS2

DO

24

—

—

—

DXS3

DO

25

—

—

—

DXS4

DO

26

—

—

—

DXS5

DO

27

—

—

—

DXS6

DO

28

—

—

—

DXS7

DO

29

—

—

—

DXS8

DO

30

DSIO (DX with
Electric Heat)
ADDRESS 49

CUST

DI

49

DXS1

DO

53

DXSD

DI

50

DXS2

DO

54

—

—

—

DXS3

DO

55

—

—

—

DXS4

DO

56

—

—

—

DXS5

DO

57

—

—

—

DXS6

DO

58

—

—

—

DXS7

DO

59

—

—

—

DXS8

DO

60

LEGEND

AFS

— Airflow Switch (Supply Fan

Status Switch)

AI

— Analog Input

AO

— Analog Output

AOTC

— Analog Output Temperature

Control

AQ1, 2 — Air Quality Sensors 1, 2
CUST

— Condensing Unit Status

(Outdoor Air Thermostat)

CWC

— Chilled Water Coil

DI

— Discrete Input

DHH

— Duct High Humidity

DO

— Discrete Output

DOTC

— Discrete Output Temperature

Control

DTCC

— Discrete Output Timeclock

Control

DXS1-8

— Direct Expansion Cooling

Stages 1-8

DXSD

— Direct Expansion Cooling

Shutdown

EHS1-8

— Electric Heater Stages 1-8

ENT

— Enthalpy Switch

EVAC

— Evacuation

FLTS

— Filter Status Switch

FSD

— Fire Shutdown

HIR

— Heat Interlock Relay

HWC

— Hot Water Coil

HUM1, 2 — Humidity Stages 1, 2
IGV

— Inlet Guide Vanes

LTT

— Low Temperature Thermostat

(also labelled FRZ)

MAT

— Mixed-Air Temperature

METER

— Meter (Pulsed Dry-Contact

Input)

MIXD

— Mixed-Air Dampers

OARH — Outdoor-Air Relative Humidity
OAT

— Outdoor-Air Temperature

OAVP

— Outdoor-Air Velocity Pressure

PRES

— Pressurization

PURG — Purge
RAT

— Return-Air Temperature

RFVC

— Return Fan Volume Control

RH

— Relative Humidity

RVP

— Return Velocity Pressure

SAT

— Supply-Air Temperature

SF

— Supply Fan Relay

SP

— Static Pressure

SPT

— Space Temperature

SVP

— Supply Velocity Pressure

TEMP

— Optional Temperature Input

*Available on VAV only.
†Discrete output with two-position damper control.

12