Carrier 39L User Manual

Page 107

Advertising
background image

Table 20 — Test of Output Options Using Option Module

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS/ACTION

RFVC X

RFVCTEST

Verify that the return fan IGVs stroke to their fully open position.

HUM1 %

The return fan IGVs should close.

HUM1TEST

Verify that the return fan IGVs, if so equipped, return to their fully closed position. If equipped with single- stage
analog humidification control, verify that the modulating valve goes to its fully open position. If equipped with
two stages of humidification, use an ohmmeter to verify that the reading across the 1st stage normally-open
relay contacts is less than 10 ohms.

HUM2 %

Verify that the reading across the 1st stage normally-open relay contacts is greater than 1000 ohms.

HUM2TEST

If equipped with two stages of humidification, use an ohmmeter to verify that the reading across the 2nd stage
normally open relay contacts is less than 10 ohms.

AOTC %

If equipped with two stages of humidification, verify that the reading across the 2nd stage humidification nor-
mally open relay contacts is greater than 100 ohms.

AOTCTEST

Verify that the analog device connected to this output strokes to its 100% position.

DOTC X

Verify that the analog device connected to this output strokes to its 0% position.

DOTCTEST

Using an ohmmeter, verify that the reading across the DOTC (Discrete Output Temperature Control) normally
open relay contacts is less than 10 ohms.

DTCC X

Using an ohmmeter, verify that the reading across the DOTC normally open relay contacts is greater than 1000
ohms.

DTCCTEST

Using an ohmmeter, verify that the reading across the DTCC (Discrete Timeclock Control) normally open relay
contacts is less than 10 ohms. Proceed with the testing of electric heat stages (Table 21). If the unit is not
equipped with electric heat, exit the Quick Test mode as described below:

EXIT TST

TST CMPL

Test is now completed. The unit is back under normal automatic control.

Table 21 — Electric Heater Test

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS/ACTION

NOTE: Only the configured number of stages are tested and appear on the display.

ELE HEAT

Entering field test of electric heater. (Set the HOA switch to AUTO.)

EHS1 X

STG1 TST

The fan starts. If equipped, the IGVs open to 30%. After an 11-second delay, the 1st stage of heat is
turned ON.

EHS2 X

The 1st stage of heat is turned OFF.

STG2 TST

After a 2-second delay, the 2nd stage of heat is turned ON.

EHS3 X

The 2nd-stage of heat is turned OFF.

STG3 TST

After a 2-second delay, the 3rd stage of heat is turned ON.

EHS4 X

The 3rd stage of heat is turned OFF.

STG4 TST

After a 2-second delay, the 4th stage of heat is turned ON.

EHS5 X

The 4th stage of heat is turned OFF.

STG5 TST

After a 2-second delay, the 5th stage of heat is turned ON.

EHS6 X

The 5th stage of heat is turned OFF.

STG6 TST

After a 2-second delay, the 6th stage of heat is turned ON.

EHS7 X

The 6th stage of heat is turned OFF.

STG7 TST

After a 2-second delay, the 7th stage of heat is turned ON.

EHS8 X

The 7th stage of heat is turned OFF.

STG8 TST

After a 2-second delay, the 8th stage of heat is turned ON.

EXIT TST

The fan and preceding stage of heat shut OFF.

TST CMPL

Test is complete. The unit is back under automatic control.

107

Advertising