Power and data distribution equipment, Ac line disconnect (200a) – PRG Controlling VARI-LITE Equipment Using DMX 512 User Manual
Page 34

DMX512 R
EFERENCE
G
UIDE
2 6
02.3004.0300.54
Power and Data Distribution Equipment
AC Line Disconnect (200A)
CAUTION: Although the maximum operating limit is 200A, we recommend that continuous
operating current does not exceed 150A.
The 200A AC line disconnect is a safety device containing a
three-phase, 200A circuit breaker serving as a master on/off
switch for the system. The unit connects to house service
through a set of five, 10-foot, 2/0 pig tails. The line disconnect
connects to the ACS rack through a set of five, 20-foot and/or
80-foot, 2/0 pig tail cable assemblies. One line disconnect is
required for each 200A service.
Figure 2-1: AC Line Disconnect
OUTPUT
INPUT
Neutral (White)
X Phase (Black)
Y Phase (Red)
Z Phase (Blue)
Ground (Green)
Neutral (White)
X Phase (Black)
Y Phase (Red)
Z Phase (Blue)
Ground (Green)
Bare wire to Cam-Lok Pigtail cables
Cam-Lok to Cam-Lok
from House AC service
Pigtail cables to ACS or Mod Rack