4 thermostat and control wiring, 0 electrical supply and wiring (cont'd), 3 typical wiring diagrams (cont'd) – Reznor EEDU Unit Installation Manual User Manual

Page 20: Form i-eedu, page 20

Advertising
background image

Form I-EEDU, Page 20

LOW

1

3

12

CR

BR

BR

Y

O

O

40 VA. CONTROL

BK

BL

24V

LINE VOLT

BR

R

TRANSFORMER

Y

BK

BK

LIMIT CONTROL

2

4

CONTACTS

VENTER RELAY

FOR WIRING)

W

BK OR R

BK

BK

LINE/1/60

L2

(COM)

L1

(HOT)

O

O

O

BL

PRESSURE

SWITCH

G

LINE GND

OPERATING SEQUENCE
- SET THERMOSTAT SWITCH AT "OFF" POSITION.

- TURN ON MAIN AND PILOT MANUAL GAS VALVES.

- TURN ON POWER TO UNIT.

- SET THERMOSTAT SWITCH AT "ON" POSITION.

- LOW STAGE OF THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.

- PRESSURE SWITCH CLOSED ENERGIZING THE PILOT GAS VALVE AND SPARK GAP

TO PRODUCE A PILOT FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE

PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY

SWITCH PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE

SPARK GAP AND ENERGIZES THE LOW STAGE GAS VALVE.

NOTES

- DOTTED WIRING SUPPLIED AND INSTALLED BY OTHERS.

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

A TEMPERATURE RATING OF A LEAST 105 DEGREES C., EXCEPT FOR

SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.

- LIMIT WIRE TO BE #18 GA. 200 C. SF-1 OF SEW-1.

- USE #14 GA. WIRE FOR LINE WIRING TO UNIT.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZES SHOULD BE OF A SIZE

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

ON 115V. UNITS THE CONTROL TRANSFORMER IS SINGLE VOLTAGE PRIMARY.

USE BLACK AND YELLOW LEADS FOR 115V.

SECONDARY SIDE OF TRANSFORMER (24V.) USE BLUE AND BROWN LEADS.

12

11

10

9

8

13

14

15

16

17

18

19

20

21

22

VENTER

RELAY COIL

9

TOTAL WIRE MINIMUM RECOMMENDED

LENGTH WIRE SIZE

150 FEET #18 GA.

250 FEET #16 GA.

350 FEET #14 GA.

FIELD CONTROL WIRING

- ON 75-250 208V UNITS, THE VENTER MOTOR WIRES ARE BLACK AND WHITE (CAP RED)

ARE BLACK AND WHITE.

ON 75-250 230V UNITS, THE VENTER MOTOR WIRES ARE RED AND WHITE (CAP BLACK)

ON 75-250 115V UNITS AND 300-400 UNITS ALL VOLTAGES, THE VENTER MOTOR WIRES

- HIGH STAGE OF THERMOSTAT CALLS FOR HEAT ENERGIZING THE HIGH STAGE

GAS VALVE, FIRING UNIT AT FULL RATE.

R

BR

W1

W2

OPTIONAL

TWO

ST

AGE THERMOST

AT

R

R

HIGH

BL

BK OR R

(SEE NOTES

VENTER MOTOR

HIGH S

TG

HI

PV

PIL

O

T

STG

LO

W

C

MV

REDUND

ANT

GAS V

AL

VE

HONE

YWELL T

WO

ST

AGE

PIL

O

T

AL

TERNA

TE

W

.R. T

WO

ST

AGE

REDUND

ANT

GAS V

AL

VE

R

BL

3

HIGH S

TG

4

BK

STG

2

LO

W

1

BR

PILOT

- FAN CONTROL KEEPS THE BLOWER CIRCUIT ENERGIZED WHILE THE UNIT IS HOT.

- BLOWER MOTOR ENERGIZED FROM HEAT EXCHANGER TEMPERATURE.

FAN CONTROL

CONTACTS

TO

BLOWER CIRCUIT

OPTIONAL

LOAD

LINE

FACTORY WIRING

FIELD WIRING

BROWN - BR

RED - R

ORANGE - O

YELLOW - Y

GREEN - G

BLUE - BL

PURPLE - PR

WHITE - W

WIRING CODE

BLACK - BK

BL

BK

BR

C

IGNITION

CONTROLLER

PROBE

GND

SPARK

FLAME SENSING

MV/PV

MV

SENSE

TH

PV

24V GND

BR

GND BURNER

G

BURNER

GROUND

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE

SPARK GAP.
ON UNITS EQUIPPED WITH LOCKOUT CONTROL, IF PILOT IS NOT

ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR ONE

HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO

THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)

EEDU AH2/AH3-AG2-CL22-CQ1 WD#110824 REV. #6

FIGURE 18B - Two Stage with Intermittent Spark Pilot System with or without Lockout

7.3 Typical Wiring Diagrams (cont'd)

7.0 Electrical Supply and Wiring (cont'd)

7.4 Thermostat and

Control Wiring

A thermostat is not standard equipment but is an installation requirement. Use either

an optional thermostat available with the heater or a field-supplied thermostat. Install

according to the thermostat manufacturer's instructions.

A 24 volt thermostat must be used to actuate low voltage gas controls. If line voltage

from the thermostat to the unit is desired, consult the factory representative.

Labeled thermostat leads are provided in the heater junction box for connection of

thermostat wiring.

Thermostats should be located five feet (1.5M) above the floor on an inside wall, not

in the path of warm or cold air currents, not in corners where air may be pocketed.

Do NOT install thermostat on cold air walls. For specific connection details, refer to

instructions with the thermostat.
If more than one unit is cycled from one thermostat, separately activated relays must

be substituted at unit thermostat connections.
If using a low voltage thermostat with a heat anticipator, set the anticipator at full load

control amps.

CAUTION: If

applicable, make sure

the thermostat has an

adequate VA rating for

the total requirements.

Add coil rating of

al relays and match

thermostat rating. See

Hazard Levels, page 2.

Advertising