8.5 Pilot and Ignition Systems

A gas-fired intermittent pilot is standard. The vertical pilot is located under the aeration

panel on the control end of the burner tray and is accessible only after the burner rack

has been removed. Remove the pilot for maintenance or service, such as checking the

wiring and cleaning. (See Paragraph 10.2.2) Pilot is target type with lint-free feature.

Pilot gas pressure should be the same as supply line pressure. (See Paragraph 6.1) If

required, adjust the pilot flame length to approximately 1-1/4" with the pilot adjustment

screw in the control valve body.
Intermittent Spark Ignition Safety Pilot Systems -- There are two types of intermit-

tent spark pilots -- one type shuts off the pilot gas flow between the cycles and the

other not only shuts off the pilot gas flow between cycles but also has a lockout device

that stops the gas flow to the pilot if the pilot fails to light in 120 seconds. The lockout

feature has a 1-hour retry or requires manual reset by interruption of the control circuit.

Propane units require the spark ignition with lockout.
Ignition Controller -- As part of the intermittent safety pilot systems, the ignition con-

troller provides the high voltage spark to ignite the pilot gas and also acts as the flame

safety device. After ignition of the pilot gas, the ignition controller electronically senses

the pilot flame. A low voltage DC electrical signal is imposed on the separate metal

probe in the pilot assembly. The metal probe is electrically insulated from ground. The

pilot flame acts as a conduction path to ground completing the DC circuit and proving

pilot flame. With pilot flame proven, the ignition controller energizes the main gas valve.

Service NOTE: If replacing

an earlier model of ignition

controller, order replace-

ment kit

P/N 257472 for

a unit with recycling gas

control Option AH2 or

P/N

257473 for Option AH3 gas

control with lockout. (Option

codes are listed on the unit

wiring diagram.)

Recycling Ignition

Controller, UTEC

1003-638A, P/N

257009, for Option

AH2 Gas Control

Ignition Controller with

Lockout, UTEC 1003-

514, P/N 257010, for

Option AH3

Gas Control

FIGURE 24 - Ignition Controllers

8.0 Controls

(cont'd)

8.6 Burner

Carryover

System and Air

Adjustment

If no spark, check the following:

a) Voltage between Terminals TH and 7 should be at least 20 volts and no higher

than 32 volts. Refer to troubleshooting (Paragraph 10.3) if no voltage is observed.

b) Short to ground in the high tension lead and/or ceramic insulator.

c) Pilot spark gap should be approximately 7/64".
If the above conditions are normal and no spark occurs, replace the ignition controller

(See

Service NOTE on the left above).

NOTE: When checking for

spark with the pilot burner

removed from the burner

rack, the pilot assembly

must be grounded to the

heater for proper spark.

8.6.1 Burner Carryover

These duct furnaces have individually formed steel burners with accurately die-formed

ports to give controlled flame stability without lifting or flashback with either natural or

propane gas. The burners are lightweight and factory mounted in an assembly which

permits them to be removed as a unit for inspection or service.

All burners are equipped with two flash carryover systems that receive a supply of gas

simultaneously with the main burner. During regular service, check the main burner

ports, the carryover assemblies, and the orifices for cleanliness.

8.6.2 Burner Air Adjustment

Burner air shutters are not normally required on natural gas furnaces. Air shutters are

supplied on propane gas units and may require adjustment.

Before making any adjustments to the air shutters, allow the heater to operate for

about fifteen minutes with the air shutters open. The slotted screw on the end mani-

fold bracket moves the air shutters and adjusts all burners simultaneously. Turning

the screw clockwise opens the shutters; counterclockwise closes the shutters. After

the furnace has been in operation for 15 minutes, close the air shutters observing

the flame for yellow-tipping. Open the shutters until the yellow disappears. A limited

amount of yellow-tipping is permissible for propane gas. Other fuels should not display

any yellow-tipping.
When making the adjustment, close the air shutters no more than is necessary to elimi-

nate the problem condition.

DANGER

Failure to install

and/or adjust air

shutters according

to directions could

cause property

damage, personal

injury, and or death.