Manifold pressure setting, Manifold or orifice pressure settings, Sizing gas supply lines – Reznor XE Unit Installation Manual User Manual

Page 16: Figure 16 - gas connection location, indoor model

Advertising
background image

Form I-XE/CRGB/RPB, P/N 131782 Rev 5, Page 15

Sizing Gas
Supply Lines

Pipe joint compounds (pipe dope) shall be resistant to the ac-
tion of liquefied petroleum gas or any other chemical con-
stituents of the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of
the unit control system, as shown in FIGURES 16 and 17. The
1/8" plugged tapping in the shutoff valve provides connection for
supply line pressure test gauge. The National Fuel Gas Code re-

FIGURE 16 - Gas Connection Location, Indoor Model

Thermostat Wire

Manual Shutoff Valve

with 1/8” NPT plugged

tapping must be installed

above unit casing.

Line Voltage

(Supply)

Junction

Box

To Gas Controls

and Burner

Ground

Joint

Union

Top View

Side View

4” (102mm)

2-3/32” (53mm)

5-5/8” (143mm)

6-7/8” (175mm)

7/8” (22mm) dia. 1-7/8” x 1-3/8” (48x35mm)

Minimum 1” (25mm) clearance between

heater access panel and elbow or fitting

Install a 1/8” NPT plug with tap

for test gauge immediately upstream

of the gas supply connection

Manual shutoff valve

Installer supplies

manual shutoff,

ground unions

and shaded piping

Gas Supply

Entrance

5

-3/4”

(146mm)

Condensate

Weep Holes

FIGURE 17 - Gas Connection Location, Outdoor Models

Install the gas supply piping
so that when the union is
disconnected, the supply pipe
will not interfere with the
removal of the burner rack.
(The burner rack slides out
of the control side of the
furnace.)

Sizes

Natural Propane

Sizes

Natural Propane

75-250

1/2"

1/2"

300-400

3/4"

1/2"

Gas Connection to S ingle-S tage Valve (Not Gas Supply Line Size)

Applies to all M odels in this M anual

quires the installation of a trap with a minimum 3" (76mm) drip leg. Local
codes may require a minimum drip leg longer than 3" (76mm), typically 6"
(152mm).
After all connections are made, disconnect the pilot supply at the control
valve and bleed the system of air. Reconnect the pilot line and leak-test all
connections by brushing on a soap solution.

WARNING: All components of a gas supply system
must be leak tested prior to placing equipment in
service. NEVER TEST FOR LEAKS WITH AN
OPEN FLAME. Failure to comply could result in
personal injury, property damage or death.

Capacity of Piping

Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

Diameter of Pipe

of 1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

Pipe

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20'

92

56

190

116

350

214

730

445

1100

671

2100

1281

30'

73

45

152

93

285

174

590

360

890

543

1650

1007

40'

63

38

130

79

245

149

500

305

760

464

1450

885

50'

56

34

115

70

215

131

440

268

670

409

1270

775

60'

50

31

105

64

195

119

400

244

610

372

1105

674

70'

46

28

96

59

180

110

370

226

560

342

1050

641

80'

43

26

90

55

170

104

350

214

530

323

990

604

90'

40

24

84

51

160

98

320

195

490

299

930

567

100'

38

23

79

48

150

92

305

186

460

281

870

531

125'

34

21

72

44

130

79

275

168

410

250

780

476

150'

31

19

64

39

120

73

250

153

380

232

710

433

175'

28

17

59

36

110

67

225

137

350

214

650

397

200'

26

16

55

34

100

61

210

128

320

195

610

372

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.

Manifold or Orifice Pressure Settings

Measuring gas valve outlet (manifold) pressure cannot be done until
the heater is in operation. It is included in the "Check-Test-Start"
section, Paragraph 30. The following instructions apply.

WARNING: Manifold gas pressure must never
exceed 3.5" w.c. for natural gas and 10" w.c. for
propane gas.

For Natural Gas: When the heater leaves the factory, the combination
valve is set so that the outlet gas pressure of a single-stage valve or high fire
of a two-stage valve is regulated to 3.5" w.c. Low fire on a two-stage valve
is set to 1.8" w.c. Inlet supply pressure to the valve must be a minimum of
5" w.c. or as noted on the rating plate and a maximum of 14" w.c. NOTE:
Always check the rating plate for minimum gas supply pressure.
Mini-
mum supply pressure requirements vary based on size of burner and the
gas control option. Most units require a minimum of 5" w.c. of natural gas

Advertising