Form I-XE/CRGB/RPB, Page 18

Typical Wiring Diagrams (Refer to the diagram supplied with the furnace for alternate controls or
optional equipment details.)
Model XE/HXE, Indoor, Gravity-Vented Furnace with Single-Stage Gas Valve

12. Electrical Supply and Connections (cont'd)

Wiring Requirements for Maxitrol Systems (cont'd)

Remote Console

If the unit being installed includes an optional console, it is shipped
separately for field installation. All consoles include indicator lights for
the blower and burner. Consoles may include a dirty filter indicator
light, a cooling indicator light, an on/off switch, a summer/off/winter

switch, a heat/vent/cool switch, a potentiometer, a thermostat, and/or a
Maxitrol temperature selector. Consoles are shipped separately for
remote installation and may be either mounted on a wall or recessed.

Field Control Wiring - Length and Gauge

Total Wire

Length

Distance from

Unit to Control

Minimum Recommended

Wire Gauge

150 ft (46M )

75 ft (23M )

#18 gauge

250 ft (76M )

125 ft (38M )

#16 gauge

350 ft (107M )

175 ft (53M )

#14 gauge

225631

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

B

W

4

11

11

Y

Y

BL

BK

BL

R

7

7

7

BK

BR

21

H

TD

H

BR

GRND.

BR

RECYCLE

G67BG-5

OR

LOCKOUT

IGNITION

CHASSIS GRND.

CONTROLLER

G770NGC-4

1

3

2

4

W

G

PROBE

GRND

IGNITOR

STRIP

FLAME SENSING

BR

BK

BL

15

FAN TD

HEATER

CR

15

7

CONTACTOR COIL

BLOWER MOTOR

7 - 8 - 9

MAIN

PILOT

BR

7

R

LIMIT

CONTROL

8

BL

R

BR

LINE V

24V

R

Y

Y

BK

BK

BL

BR

12

MANUAL RESET

BLOCKED

VENT SWITCH

Y

40 VA CONTROL

TRANSFORMER

SET ANT. AT 0.8 AMPS

OPT. SINGLE STAGE

THERMOSTAT

R

W

8

10

10

8

R

1/60 OR 3/60

LINE

GRD

G

R OR W

R OR BK

R

PROTECTED

BLOWER

MOTOR

INTERNALLY

CONTACTOR

BLOWER MOTOR

CONTACTS

L2

L3

L1

Y

BK

BK

T1

T2

T3

OPTIONAL

SUMMER/WINTER

SWITCH

PV

PILOT

MV

PV-MV

MAIN

REDUNDANT

GAS V

A

LV

E

HONEYWELL

BK

BK

(SEE NOTES)

DISCONNECT SWITCH

CONTACTS

FAN TD

1

3

TOTAL WIRE MINIMUM RECOMMENDED

LENGTH WIRE SIZE

150 FEET #18 GA.

250 FEET #16 GA.

350 FEET #14 GA.

FIELD CONTROL WIRING

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

9. ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

7. USE #12 GA. WIRE FOR LINE AND MOTOR WIRING ON SINGLE PHASE UNIT.

6. USE #14 GA. WIRE FOR LINE AND MOTOR WIRING ON 3 PHASE UNIT.

PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

5. LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO

TEMPERATURE RATING OF AT LEAST 105° C., EXCEPT FOR

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A

4. CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

3. DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

2. THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT:

1. THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

THERMOSTAT AND SUMMER / WINTER SWITCH

BLOCKED VENT SWITCH AND SENSOR LEAD WIRE WHICH MUST BE 150°S C.

8. USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: NONE

NONE

NOTES

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

TIMES THE MAXIMUM TOTAL INPUT AMPS.

10. WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

11. DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.

2. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE

SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE SPARK GAP.

ON UNIT EQUIPPED WITH G770NGC-4 LOCKOUT CONTROL, IF PILOT IS

NOT ESTABLISHED WITHIN 120 SECONDS (APPROX.) UNIT LOCKS OUT

AND MUST BE RESET BY INTERRUPTING POWER TO CONTROL CIRCUIT

(SEE LIGHTING INSTRUCTIONS).

OPERATING SEQUENCE

1. SET THERMOSTAT AT LOWEST SETTING.

2. TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.

1. ON A CALL FOR HEAT BY THE THERMOSTAT.

(A) THE PILOT GAS VALVE AND SPARK GAP ARE ENERGIZED TO PRODUCE A PILOT

FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE

PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY PORTION OF

THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE SPARK GAP AND

ENERGIZES THE MAIN VALVE. THE MAIN GAS IGNITES AND UNIT FIRES AT

4. SET THERMOSTAT AT LOWEST SETTING FOR SHUTDOWN.

(B) THE BLOWER MOTOR OPERATES FROM FAN TIME DELAY.

3. SET THERMOSTAT AT DESIRED SETTING.

FIRING SEQUENCE:

FULL RATE.

(A) FIRING RATE IS CONTROLLED BY THE THERMOSTAT.

5. SET SUMMER / WINTER SWITCH AT "ON" POSITION (CLOSED) FOR CONTINUOUS

BLOWER OPERATION.

(A) BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.

REDUNDANT

GAS V

A

LV

E

AL

TERNA

TE W

.R. OR ROBER

TSHA

W

BL

P

BK

BR

MAIN

PILOT

M

C

XE: AH2/AH3-AG1-CH1-CL1 DWG. #225631

RSM

OPTIONAL FIELD WIRING

OPTIONAL FACTORY WIRING

FACTORY WIRING

FIELD WIRING

TERMINAL BLOCK -- HEATER COMPARTMENT

4, 7, 8, 10, 11,

12, B & W

may cause the unit to function erratically or may destroy the amplifier.
If shielded wires are used, shield must be insulated and grounded at the
amplifier location only.