Optional filter rack and filters – Reznor XE Unit Installation Manual User Manual

Page 38

Advertising
background image

Form I-XE/CRGB/RPB, P/N 131782 Rev 5, Page 37

4. Adjustment of the Switch - The "HIGH" actuation point of the

null switch is indicated on a calibrated scale secured to the trans-
parent range screw enclosure. Building pressure is set by turning
the adjustment screw. The "Low" actuation point is set by adjust-
ing the span of the null by turning the span adjustment screw. The
span range is .01 to .03" w.c.

IMPORTANT: To eliminate shipping damage to the switch contacts,
the manufacturer reduced the span adjustment to zero before ship-
ping. The span should be adjusted prior to using the switch. (If the
switch has been installed, disconnect the vent tube so that the null
switch is in a neutral position.) Remove the electrical box cover and
while observing the contacts, turn the span adjustment screw slowly
in a clockwise direction. Continue turning the adjustment screw until
you are able to see gaps between the common and both the low and
high contacts. A minimum gap provides the greatest sensitivity. The
wider the gap the lower the sensitivity.

5. See the wiring diagram included with the furnace to make electrical

connections.

A

C

D

B

F1

F2

25”

(635mm)

20” (508mm)

34”

(864mm)

E

A

C

F1

F2

B

D

25”

(635mm)

20” (508m

m)

34”

(864m

m)

20”

(508mm)

34”

(864mm)

F2

F1

A

20” (508mm)

B

35. Optional Filter Rack and Filters

35A. Filter Rack and Filters - Indoor Models
XE/HXE

Filter racks and filters are factory installed optional equipment on
indoor systems. 1" or 2" disposable, pleated disposable, or perma-
nent filters are available. For pressure drops, see the chart for outdoor
models in Paragraph 35B.

FIGURE 42A - Filter
Arrangement

Indoor
Sizes 75,
100, 125,
150, 175

FIGURE 42B - Filter
Arrangement

Indoor Sizes
200, 225,
250, 300,
350

FIGURE 42C -
Filter Arrangement

Indoor
Size 400

35B. Filter Rack and Filters - Outdoor Model
Series CRGB and RPB

Filter rack and filters are factory installed optional equipment. Filters are
available in 1" or 2" disposable, 1" or 2" permanent aluminum, and 1" or 2"
pleated disposable.
Tested in accordance with ASHRAE 52-76 Test Standard, the filters pro-
vided have the specifications shown in the table on the right.
Size, quantity, and pressure drops of filters for outdoor models are in the
table below. Refer to FIGURE 43, for filter arrangements.

Filter Pressure Drops (" w.c.)

Heater

Filter Size

Metal Fillers

Size

A

B

C

D

E

F1

F2

75,100,125 20x20 20x20

--

--

--

--

--

150, 175

20x25 20x25

--

--

--

13/16

13/16

200, 225

16x25 16x20 16x25 16x20

--

--

--

250, 300

20x25 20x20 20x25 20x20

--

--

--

350

20x25 20x25 20x25 20x20

--

4-13/16

--

400

16x25 20x25 16x25 20x25 16x25

2-5/8

1-1/16

D is p o s a b le

P le a t e d

1"

2"

1"

2"

1"

2"

575

0.00

0.00

0.01

0.01

0.02

0.01

75

(1) 20x25

1000

0.00

0.01

0.02

0.03

0.05

0.04

100

(1) 25x25

1500

0.01

0.02

0.04

0.06

0.12

0.08

125

2000

0.01

0.02

0.08

0.11

0.22

0.15

2500

0.02

0.03

0.12

0.17

0.34

0.23

3000

N/A

N/A

0.17

0.24

0.49

0.33

3500

N/A

N/A

0.24

0.34

0.67

0.45

4000

N/A

N/A

0.31

0.43

N/A

N/A

1175

0.00

0.01

0.02

0.03

0.05

0.03

150

(2) 16x20

1500

0.01

0.01

0.04

0.06

0.07

0.05

175

(2) 16x25

2000

0.01

0.02

0.06

0.08

0.13

0.09

2500

0.02

0.03

0.10

0.14

0.20

0.14

3000

0.03

0.04

0.14

0.20

0.34

0.23

3500

0.04

0.05

0.20

0.28

0.40

0.27

4000

0.05

0.07

0.26

0.36

0.52

0.36

4500

N/A

N/A

0.32

0.45

0.66

0.45

5000

N/A

N/A

0.36

0.54

0.82

0.56

1550

0.01

0.01

0.03

0.04

0.06

0.04

200

(1) 16x20

2000

0.01

0.01

0.05

0.07

0.10

0.07

225

(1) 16x25

2500

0.01

0.02

0.08

0.11

0.16

0.11

(1) 20x20

3000

0.02

0.03

0.11

0.16

0.23

0.16

(1) 20x25

3500

0.03

0.04

0.15

0.22

0.31

0.21

4000

0.04

0.05

0.20

0.28

0.40

0.27

4500

0.05

0.06

0.26

0.36

0.51

0.35

5000

N/A

N/A

0.32

0.44

0.63

0.43

5400

N/A

N/A

0.37

0.52

0.74

0.50

1950

0.01

0.02

0.03

0.05

0.07

0.05

250

(1) 20x20

2500

0.02

0.03

0.06

0.08

0.11

0.08

300

(3) 20x25

3000

0.03

0.04

0.08

0.12

0.16

0.11

3500

0.04

0.05

0.10

0.16

0.22

0.15

4000

0.05

0.07

0.15

0.21

0.29

0.20

4500

0.06

0.09

0.19

0.26

0.37

0.25

5000

0.08

0.11

0.23

0.32

0.45

0.31

5500

N/A

N/A

0.28

0.39

0.55

0.37

6000

N/A

N/A

0.33

0.46

0.65

0.44

6500

N/A

N/A

0.39

0.54

0.77

0.52

2750

0.02

0.03

0.06

0.08

0.12

0.08

350

(2) 16x25

3500

0.03

0.04

0.09

0.13

0.19

0.13

(3) 20x25

4000

0.04

0.06

0.12

0.17

0.25

0.17

4500

0.06

0.07

0.15

0.21

0.32

0.22

5000

0.07

0.09

0.19

0.26

0.40

0.27

5500

0.08

0.10

0.23

0.32

0.48

0.33

6000

0.08

0.12

0.27

0.38

0.57

0.39

6500

N/A

N/A

0.32

0.44

0.67

0.46

7000

N/A

N/A

0.37

0.51

0.78

0.53

3100

0.04

0.04

0.06

0.08

0.12

0.08

400

(1) 16x20

3500

0.05

0.06

0.08

0.11

0.16

0.11

(1) 16x25

4000

0.06

0.07

0.10

0.14

0.21

0.14

(2) 20x20

4500

0.08

0.09

0.13

0.18

0.26

0.18

(2) 20x25

5000

0.10

0.12

0.16

0.22

0.32

0.22

5500

0.12

0.14

0.19

0.27

0.39

0.27

6000

0.14

0.17

0.23

0.32

0.46

0.32

6500

0.17

0.20

0.27

0.38

0.54

0.37

7000

0.20

0.23

0.31

0.44

0.63

0.43

7400

N/A

N/A

0.35

0.49

0.71

0.48

Heater

S ize

Qty & S ize

of Filters

CFM

P e rm a n e n t

Advertising