Electrical supply and connections, Thermostat and connections, Fan motor – Reznor FT Unit Installation Manual User Manual

Page 12: Circuit board led flash codes, Dip switch settings

Advertising
background image

Form RZ-NA-I-FT, Mfg No. 173473 Rev 8, Page 11

3. With the manual valve positioned to prevent flow to the main burn-

ers, connect a manometer to the 1/8” pipe outlet pressure tap in the

valve. Use a water column manometer that is readable to the near-

est tenth of an inch.

4. Remove the cap from the pressure adjusting screw and adjust the

manifold pressure to the pressure setting selected from the table.

Cycle the main burners once or twice to properly seat the adjust-

ment spring in the valve.

Re-check the pressure. If necessary, re-adjust the pressure. When

the pressure is correct, remove the manometer and replace the cap.

Check for leaks at the pressure tap fitting.

5. With the heater operating determine that the inlet pressure to the

heater for natural gas is between 5 and 13.5 in. w.c. and for propane

between 10 and 13.5 in. w.c. Take this reading as close as possible

to heater (Most heaters are now equipped with gas valves that have

an inlet pressure tap.) If the inlet pressure is not within the speci-
fied range, the inlet pressure must be corrected and Steps 3 and 4
repeated.

6. If altitude is above 6000 ft (1830M), verify that the pressure switch

has been changed.

High Altitude Combustion Air Pressure Switches
FT

P/N

Description

30

164674 Blue Label, -.10", #PPS10027-2733

45-60

164675 Brown Label, -.17", #PPS10027-2734

75-200

149879 Orange Label, -.50", #PPS10027-2355

250-300 151372 White Label, -.74", #PPS10027-2406

7. Find the Manifold Pressure Adjustment label in the plastic bag that

contained these instructions. Using a permanent marker, fill-in the

pressure setting. Adhere the label on the heater near the gas valve

so that it is conspicuous to someone servicing the valve.

13. Electrical Supply and

Connections

All electrical wiring and connections, including electrical grounding

MUST be made in accordance with the National Electric Code ANSI/

NFPA No. 70 (latest edition) or, in Canada, the Canadian Electrical

Code, Part I-C.S.A. Standard C22.1. In addition, the installer should

be aware of any local ordinances or gas company requirements that

might apply.

Figure 9 - Electrical Connections, DIP Switch Settings, and LED Signal Codes on the Integrated Circuit Board in
the Control Compartment

Circuit Board LED Flash Codes

Slow Flash .....

Normal Operation, No Call for Heat

Fast Flash ......

Normal Operation, Call for Heat

2 Flashes ........

System Lockout, Failed to Detect or Sustain Flame

3 Flashes .........

Pressure Switch Open or Closed

4 Flashes .........

High Limit or Flame Rollout Switch Open

5 Flashes .........

Flame Sensed and Gas Valve Not Energized

Steady On .......

Internal Failure - Replace the Circuit Board

DIP Switch Settings

SW1

Fan Delay

1

2

to Off

OFF

OFF

90 seconds

OFF*

ON*

120 seconds*

ON

OFF

180 seconds

ON

ON

240 seconds

*Standard factory setting.

DIP Switch for
Regulating Fan Off
Delay Time

Check the rating plate on the heater for the supply voltage and current

requirements. A dedicated line voltage supply with fused disconnect

switch should be run directly from the main electrical panel to the heater.

All external wiring must be within approved conduit and have a mini-

mum temperature rise of 60°C

.

Conduit from the disconnect switch

must be run so as not to interfere with the service panels of the heater.
The electrical supply and control wiring enter at the rear of the heater

and connect to the integrated circuit board. The 115 volt supply wiring

connects to pigtails on the lower portion of the circuit board. The ter-

minal strip for 24 volt thermostat connections is located on the upper

portion of the circuit board. See Figure 9.

CAUTION: Route the wires so that they do not
contact the flue wrapper or venter housing.

Consult the wiring diagram supplied with your heater. A typical wiring

diagram is on page 12.

CAUTION: If any of the original wire as supplied
with the appliance must be replaced, it must be
replaced with wiring material having a temperature
rating of at least 105°C, except for limit control and
sensor lead wires which must be 150°C. See Hazard
Levels, page 1.

14. Thermostat and Connections

A thermostat is not standard equipment but is an installation require-

ment. Use either an optional thermostat available with the heater or a

field-supplied 24-volt thermostat. Install according to the thermostat

manufacturer's instructions, paying particular attention to the require-

ments regarding the location of the thermostat.
Make sure that the heat anticipator setting on the thermostat is 0.6

amps (or in accordance with the amperage value noted on the wiring

diagram of your heater).

15. Fan Motor

The fan motor is equipped with thermal overload protection of the au-

tomatic reset type. Should the motor refuse to run, it may be because of

improper current characteristics. Make certain that the correct voltage

is available at the motor.

Ignitor
Connection

Line Voltage
Connection

24-volt Terminal
Strip for
Thermostat
Connections (refer
to wiring diagram)

LED Signal

Advertising