Typical wiring diagram, Ft series reznor – Reznor FT Unit Installation Manual User Manual

Page 13

Advertising
background image

Form RZ-NA-I-FT, Page 12

Figure 10 -
Wiring
Diagram
#147203 for
Model FT,
Sizes 30 - 300

TYPICAL WIRING DIAGRAM

Fan-Type, Power-Vented Model with Direct Spark Ignition, Single-Stage Heating, Natural or
Propane Gas

VENTER MOTOR

FAN MOTOR

30 VA. CONTROL

BK

BL

24V

115 VOLT

BR

TRANSFORMER

W

CMB

ACB HEAT

LINE

GROUND

VALVE

PSW

HI LIMIT

HI LIMIT

MAIN VALVE

PRESSURE SWITCH

HIGH

LIMIT

SET ANT

. A

T 0.6 AMPS

OPT

. SINGLE ST

AGE

THERMOST

AT

W

R

S/W SWITCH

OPTIONAL SP-ST

R

G

W

24VAC

L1

(HOT)

L2

(COM)

FLAME SENSING

PROBE

FLAME SENSE

IGNITOR

HV LEAD

OPERATING SEQUENCE

1. SET THERMOSTAT AT LOWEST SETTING.

2. TURN ON MANUAL GAS VALVE.

3. TURN ON POWER TO UNIT.

4. SET THERMOSTAT AT DESIRED SETTING.

5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.

6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.

7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN

MOTOR IS ENERGIZED.

8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND

MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT

(SEE LIGHTING INSTRUCTIONS).

LED CODES

SLOW FLASH NORMAL OPERATION - NO CALL FOR HEAT

FAST FLASH NORMAL OPERATION - CALL FOR HEAT

2 FLASHES SYSTEM LOCKOUT - FAILED TO DETECT OR SUSTAIN FLAME

3 FLASHES PRESSURE SWITCH OPEN OR CLOSED

4 FLASHES OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL

5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED

STEADY ON INTERNAL FAILURE (MICRO-CONTROLLER FAILURE: SELF CHECK)

NOTES

1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT

2. DOTTED WIRING INSTALLED BY OTHERS.

3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE

APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL

HAVING A TEMPERATURE RATING OF AT LEAST 105°C. EXCEPT FOR SENSOR

LEAD WIRE AND LIMIT WIRING WHICH MUST BE 150°C.

4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.

5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT

VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

FIELD CONTROL WIRING

150'

250'

350'

75'

125'

175'

#18 GA. WIRE

#16 GA. WIRE

#14 GA. WIRE

TOTAL WIRE

LENGTH

DISTANCE FROM

UNIT TO CONTROL

MIN. RECOMMENDED

WIRE GAUGE

ROLLOUT

LED

BK

BK

BK

BL

BL

BL

BK

BL

R

Y

Y

R

BR

BR

BK

BK

BK

BK

BK

BR

R

Y

BL

WIRE NUT

FIELD WIRING

OPTIONAL FACTORY WIRING

FACTORY WIRING

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

BR

R

GRD

G

115/1/60

W.D. 147203 REV. #6

CHASSIS GRND.

BURNER GROUND

W

W

W

(SEE NOTE 6)

6. THESE WIRE NUTS ARE NOT USED ON ALL MODELS.

BK

FT SERIES

REZNOR

IN

OUT

VAC HOT

HOT

IN

BLWR AUX

FLAME ROLLOUT SWITCH

(MODELS 30 - 60)

LIMIT

HIGH

250 & 300)

(MODELS

DSI CONTROL

ON OFF 180 SECONDS

ON ON 240 SECONDS

OFF OFF 90 SECONDS

OFF ON 120 SECONDS (FACTORY SETTING)

1 2 FAN DELAY TO OFF

SW1

DIP SWITCH SETTINGS

SW1