8. Left Side Controls

All units are factory built with controls on the right side (as

viewed when facing the heater discharge). If the installation

location requires that the controls be on the left side, follow

the steps below to change the control side.
1. Turn the heater over (180

o

)

. Turn so that the sides are

opposite but the front and rear remain the same. (Notice

that the "bottom" panel, which is now on the top of the

heater, has four suspension holes.)

2. Reverse the Louver Position

-- Remove the screws hold-

ing the louver frame. Turn the louver assembly (180

o

). Re-

install the assembly so that the louvers will direct the air

downward with the heater in its new position.

3. Sizes 60, 75, 100, 125, 150, 200, 250 and 300; Move the

Ignitor

-- Remove the control access panel. On the side of

the burner rack, remove the screws holding the spark igni-

tor and the flame sensor. Interchange the locations of the

ignitor and the flame sensor so that the ignitor will be to-

ward the bottom of the burner rack. IMPORTANT: The
brown ground wire must
stay with the spark ignitor.

4.

Turn the access panel so that the labels are in an upright

position. Re-attach the panel (NOTE: Illustrations of the

control section, except for the location of the ignitor and

the flame sensor on Sizes 60-300, will appear to be upside

down.)

9. Suspending the Heater

Before suspending the heater, check the supporting structure

to be used to verify that it has sufficient load-carrying capac-

ity to support the weight of the unit.

When the heater is lifted for suspension, support the bottom of the heater with

plywood or other appropriately placed material. If the bottom is not supported,

damage could occur.
Determine the type of suspension to be used:

All Sizes

- The heater is equipped with 4-pt suspension. Two 3/8"-16 nut

retainers are located on each side of the heater. See Dimensions in Paragraph

10 and illustration in Figure 3A.

Sizes 30, 45, 60, and 75

may be installed with 2-pt suspension. Follow the

illustrated instructions in Figure 3B.

Sizes 30, 45, 60, and 75

may be suspended with an optional ceiling sus-

pension kit. Refer to Figure 3C. Step-by-step instructions are included with

the option kit.

WARNING: Suspend any size of Model FT heater only
from the threaded nut retainers (Figure 3A). Or, suspend
a Size 30, 45,60, or 75 as illustrated in Figure 3B or using
the Ceiling Suspension Kit in Figure 3C. Do not suspend
from the heater cabinet panels.

WARNING: Unit must be level for proper operation. Do not
place or add additional weight to the suspended heater. Hazard
Levels, page 1.

3/8” Threaded Rod

Add a 3/8” nut

to lock the hanger

rod to the heater

Be sure that the 3/8" threaded hanger
rods are locked to the heater as
illustrated. Recommended maximum
hanger rod length is 6 feet.

Figure 3A -
Four-point
suspension on
all sizes; attach
threaded rods
to all four nut
retainers

Sizes 30/45 --

21-1/4” (540mm)

Sizes 60/75 --

23-1/4” (591mm)

17-15/16”

(456mm)

9-9/16”

(243mm)5/16” or 3/8” threaded rods

(maximum length above

the heater is 18”/457mm )

On the bottom of the heater, use a washer

and double nuts to attach each threaded

rod. Use double nuts. Lock lower nut to

upper by holding upper nut while

tightening lower nut.

Sizes 30/45

12-1/8”

(308mm)

Sizes 60/75

18-1/8”

(591mm)

L

C

L

C

Figure 3B - Two-point suspension
applies to Models FT 30, 45, 60,
and 75

Size 30 45 60 75 100 125 150 200 250 300

lbs 60 66 84 90 140 145 205 215 258 280

kg

27 30 38 41 64 66 93 98 117 127

Net Weight

Suspension Angle, P/N 194931 - Attach by (1) removing ALL

screws across top edge of cabinet. (2) Position suspension angle,

aligning holes with same holes emptied in Step (1). (3) Using

ALL screws that were removed and the same

cabinet holes, attach suspension angle.

Suspension angle

attached to rear

of heater

Figure 3C - Ceiling Suspension Kit, Option CK22,
for Models FT 30, 45, 60, or 75

When suspending, use a minimum of two anchor points per

angle.
NOTES: Quantity of screws used to attach the suspension angles

will vary by heater size and from front to rear of cabinet. If

optional vertical louvers are being added, install louvers after

suspension angles are attached.