Reznor FT Unit Installation Manual User Manual

Page 8

Advertising
background image

Form RZ-NA-I-FT, Mfg No. 173473 Rev 8, Page 7

NOR

5 ft (1.5M)

maximum

Thimble (if wall

is combustible)

If using single-wall pipe,

drill a 3/8” diameter hole in

elbow for water drainage.

8” (203mm)

minimum

8” (203mm) minimum

6” (152mm) minimum

Pitch horizontal pipe 1/4” per foot

toward outlet for water drainage.

3. Vent Pipe Diameter and Vent Length
Comply with all requirements that apply. Use only one diameter of vent pipe on an installation. Minimum vent length is 5 feet.

IMPORTANT Vent Length NOTES:

1) If the system contains all vertical pipe or a combination of
horizontal and vertical vent pipe

, the Maximum Permissible Vent

Length in the Table may be increased one foot for each foot of

vertical rise up to a maximum increase of ten feet.
2) If using vent pipe approved for a Category I appliance to
install a horizontal vent on a residential
application

, the maxi-

mum horizontal length is five feet (1.5M). Do not include the el-

bow used to connect the horizontal section to the vertical section in

the 5-foot limit. The vertical portion must be a minimum of 8". See
Special Requirements below and Figure 6.

Special Vent Pipe Requirements for Residential Horizontal Vent System
Using Category I Pipe (See Figure 6)
When installing pipe approved for a Category I heater in a residential hori-

zontal vent system, it is necessary to use 4" pipe only on a Size 30 and 5"

pipe only on Sizes 45 and 60. Sizes 45 and 60 will require an increaser collar

at the venter outlet. The maximum horizontal vent length for a residential

Category I vent is 5 ft (1.5M); see Figure 6.

Model

Vent

Venter

Field-supplied "increaser"

FT

Pipe

Outlet

collar required to connect

Size

Diameter

Diameter

pipe to venter outlet

30

4"

4"

No

45

5"

4"

Yes

60

5"

4"

Yes

90°

Elbows

45°

Elbows

30 ft

5 ft

2.5 ft

9 M

1.5M

.75M

30 ft

5 ft

2.5 ft

9 M

1.5M

.75M

30 ft

5 ft

2.5 ft

9 M

1.5M

.75M

40 ft

5 ft

2.5 ft

12 M

1.5M

.75M

30 ft

5 ft

2.5 ft

9 M

1.5M

.75M

40 ft

5 ft

2.5 ft

12 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

50 ft

5 ft

2.5 ft

15 M

1.5M

.75M

300

6"

Maximum Vent

Length

*Reduce the maximum vent length by the amount indicated for
each elbow used.

30

3" or 4"

45

3" or 4"

100

4"

200

5"

250

5"

125

4"

150

5"

60

75

3"

4"

3"

4"

Maximum Permissible Vent Lengths

FT

Equivalent

S traight Length*

Vent Pipe

Diameter

(se e NO TES and special

requireme nts in the right column)

Figure 6 - Horizontal Vent on a Residential Installation using Category I Vent Pipe

Size 30 requires 4" diameter vent pipe

Size 45 requires 5" diameter vent pipe

Size 60 requires 5" diameter vent pipe

Maximum horizontal vent length is 5' (1.5M)

Minimum vertical vent length is 8" (203mm)

Comply with clearances

Drill the elbow as illustrated (single-wall pipe only)