Type of pipe (field-supplied) (cont'd), Joints/seals, Pipe diameter and length - ft (m) – Reznor SFT Unit Installation Manual User Manual

Page 8: Support, Clearance

Advertising
background image

Form RZ -NA-I-SFT, Mfg No. 173474 (Rev 6), Page 7

Horizontal Vent
Terminal/Combustion
Air Package
(Option CC6)
includes:

Instructions and Requirements for Installing a Horizontal Vent Terminal/Combustion Air
Inlet (Requires Concentric Adapter Kit, Option CC6)

2. Type of Pipe (field-supplied) (cont'd)

Reducer

Enlarger

Airflow

Airflow

Either collar

or smaller

diameter pipe

Taper-type Connector

Secure joints with sheetmetal

screws and seal.

Figure 5 - Use taper-type connections (see where
they are required below)

S ize

S FT

Inlet

Air

Pipe

Air Inlet

Collar on

Concentric

Adapter

Reducer required

to join concentric

adapter collar and

pipe

Reducer required

to join heater

collar and pipe

Inlet Air
Collar at

Heater

3" dia

4" to 3" Reducer

None

4" dia

None

4" to 3" Reducer

60-125 4" dia

4" dia

None

None

4" dia

150-250 5" dia

5" dia

None

None

5" dia

300

6" dia

6" dia

None

None

6" dia

45

4" dia

3" dia

A taper-type connector is always required in the indoor portion of the INLET
AIR PIPE
on Model SFT 45. When using 3" pipe, install the reducer at the
concentric adapter. When using 4" pipe, install the reducer at the heater. Other
sizes do not require a taper-type connection in the inlet air pipe run.

run is different from the connections at either the heater or the con-
centric adapter box, the joint must be made with a taper-type pipe
connector.

When the diameter change is at the heater, install the connector at
the collar or no more than 6" (152mm) from the heater.

When the diameter change is at the concentric adapter box, install
the connector no more than 6" (152mm) from the opening or collar
on the concentric adapter box.

Concentric Pipes (the vent pipe runs through the concentric adapter
extending internally concentric through the outdoor portion of the com-
bustion air pipe)
- Sizes 45 - 250 require 6" diameter combustion air pipe
for the outdoor portion and a 4" vent pipe through the concentric adapter
to the terminal; Size 300 requires an 8" diameter combustion air pipe for
the outdoor portion and a 5" diameter vent pipe through the concentric
adapter to the terminal. Refer to the installation instructions for the con-
centric adapter kit for length requirements.

4. Joints/Seals

In Pipe Runs - provide pipe as specified in Requirement No. 2 and make
joints as follows:

If using single wall, 26-gauge or heavier galvanized pipe, secure
slip-fit pipe connections using sheetmetal screws or rivets. Seal all
joints. Seal combustion air pipe with pressure sensitive tape ordi-
narily used for warm-air ductwork. Wrap two full turns around each
joint. Seal flue exhaust pipe with either tape suitable for 550°F (such
as Option FA1, P/N 98266) or high-temperature (450°F) silicone seal-
ant.

If using Category III vent pipe, follow the pipe manufacturer's in-
structions for joining and sealing vent pipe sections.

In Concentric Pipes (outdoor portion) from the Adapter Box to Air
Inlet and Vent Terminal
- Follow the instructions for concentric adapter
kit (pages 7 - 9 for a horizontal system or pages 10 - 110 for a vertical
system).

Joints Requiring Taper-type Connections (See Figure 5 and Tables
that follow)
- When the diameter of the pipe in the inlet air or vent pipe

Combustion Air Inlet Pipe Between the Heater and the Concentric
Adapter
- Sealed, single-wall galvanized pipe is recommended.

Combustion Air Pipe Between the Adapter Box and the Combustion
Air Inlet
- The vent pipe is internally concentric to the combustion air
pipe; use single-wall galvanized pipe for the combustion air pipe.

3. Pipe Diameter and Length - ft (M)

Maximum Pipe Length from Heater to Concentric

Adapter - minimum length is five feet (1524 mm)

Model

Pipe Diameter

Maximum

90° Elbow

45° Elbow

SFT

Vent

Inlet Air

Length

Equals*

Equals*

45

3" or 4"

3"

30 ft (9.1M)

5 ft (1.5M) 2.5 ft (.8M)

60, 75,

4" or

4"

40 ft

5 ft

2.5 ft

100, 125

5"

(12.1M)

(1.5M)

(.8M)

150, 200

5"

5"

40 ft (12.1M) 5 ft (1.5M) 2.5 ft (.8M)

250

5"

5"

50 ft (15.2M) 5 ft (1.5M) 2.5 ft (.8M)

300

6"

6"

50 ft (15.2M) 5 ft (1.5M) 2.5 ft (.8M)

*Reduce maximum length by this amount for each elbow.

Qty

Size

P/N

Description

1

45-125 157157

150-250 157158

300

82131

1

45-125 155118

150-250 155392

300

68404

1

45-250 155096 Screened

300

53316 Exhaust Assy

Complete Horizontal Vent Kit

(Same as Opt ion CC6)

Concent ric Adapter Box

Assemby (See Figure 3A)

Qty

S ize

P/N

Description

1

45-250 151755 Inlet

300

124940 Guard

4

45-300

37661

#10-16 x 1/2" lg Screws to
att ach the inlet guard

1

45-250 164492 4" I.D. Rubber Seal

1

300

164493 5" I.D. Rubber Seal

1

45-300

53335

T ube of High T emperature

(450°F) Silicone Sealant

S FT

S ize

Vent

Pipe

Run

Venter

Collar

on

Heater

Reducer required

to join venter collar

and p ip e

Tap er-ty p e

connection required

to join different

diameter vent p ip es

Vent Pip e

through

Adap ter

Box

3" dia

4" to 3" Reducer

3" to 4" Enlarger

4" dia

None

None

4" dia

5" to 4" Reducer

None

5" dia

None

5" to 4" Reducer

150-250 5" dia

5" dia

None

5" to 4" Reducer

4" dia

300

6" dia

6" dia

None

6" to 5" Reducer

5" dia

Taper-typ e connector(s) required in the VENT PIPE RUN

4" dia

4" dia

60-125

45

4" dia

5" dia

5. Support

Support horizontal runs every six feet (1829mm); do not rely on the
heater or the adapter box for support of either horizontal or vertical
pipes. Use non-combustible supports on vent pipe.

6. Clearance

Do not enclose the vent pipe or place pipe closer than 6" (152mm)
to combustible material.