1 terminal strip 1 -2, 1 terminal strip 1 – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual
Page 46

SKE-Series Voice Evacuation System Installation/Operation Manual
6-2
151267
6.1.1
Terminal Strip 1
This sections describes what the terminal connections of terminal strip 1 are used for.
Terminal
Number
Name
Description
1
+24 VDC
Positive 24 VDC in or out.
2
GND
Ground
3
Trouble Out
Trouble output, active low.
4
GND
Ground
5
Select All
Not Used
6
Not Used
7
8
GND
Ground
9
GND
Ground
10
Alarm Active
Signal input from main DMR to indicate when an Alarm occurs. Active low.
11
Alarm Select 1
Used by FACP for automatic alarm control of zone outputs. Active low.
12
Alarm Select 2
13
Alarm Select 3
14
Alarm Select 4
15
Alarm Select 5
16
Alarm Select 6
17
GND
Ground
18
MIC Active
Signal input from main DMR to indicate when the microphone has been
activated. Active low.
19
Not Used
Not Used
20
Not Used
21
Not Used
22
Not Used
23
Not Used
24
Not Used