Ske-zn6 specifications -5, Mounting the ske-zn6 in the ske-450 cabinet -5 – SilentKnight SKE-450 Voice Evacuation Control Panel User Manual
Page 49
Advertising

SKE-ZN6 Six Zone Splitter Installation
151267
6-5
6.2 SKE-ZN6 Specifications
6.3 Mounting the SKE-ZN6 In the SKE-450 Cabinet
This section contains instructions on how to install the SKE-ZN6 Zone Splitter into the
SKE450 Voice Evacuation cabinet.
Follow these steps to install the SKE-ZN6 into the SKE450 cabinet:
1. Unlock and open the SKE450 control panel cabinet door.
2. Remove the control panel cover door retaining screws.
Figure 6-2 SKE450 Cabinet With Control Panel Cover In Place
3. Swing the control panel cover door open.
Circuit
Rating
Operating Voltage:
24 VDC
Current Draw:
Standby:
30 mA
Alarm:
All channels active 120 mA
Humidity
93% non-condensing max.
Control Panel
Cover Retaining
Screws
Control Panel
Cover Door
SKE-ZN6 Access
Plate
Advertising