The gas metered in 3 minutes to obtain rated input for
each boiler model, using 1000 Btu/cu. ft. gas, is tabu-
lated in gas rate table.

B. Main Burners

1. Fire the boiler continuously for at least 15 minutes, to

reach burner operating temperature.

2. Observe the flames, all burners. The base of all flame

jets should be blue. The tips should be blue shading
to orange. NOTE: Dust, disturbed by any movement,
will cause bright orange flames. Wait for dust to settle.

3. For one burner, close the air shutter until some of its

flame jet tips turn yellow-white, indicating insufficient
primary air. Then open shutter until whitish tips disap-
pear completely. Set all burner shutters to the same
opening. Observe to make sure that no yellow-white
tips appear over any portion of the flame. Small yel-
low tips at the pilot are permitted (see Figure 22).

NOTE: This adjustment method gives MINIMUM pri-
mary air setting for safe combustion. DO NOT attempt
to make this adjustment unless burners are at operat-
ing temperature. Adjustment should be made with
burner access panel in final operating position. Use of
a mirror may be helpful to observe flames. Note that
burner ports are on top of main burner tube.

C. Main Burner Ignition Checkout and Pilot Adjustment

1. The pilot flame must not smother or snuff out when

tested as follows:
a. Main burner ignition from cold start-repeat.
b. Continued operation of main burner.
c. Main burner ignition with appliance at maximum

operating temperature after prolonged operation.

NOTE: Observe operation of the pilot burner with
appliance doors in the final operating position. Use of
a mirror may be helpful.

2. Pilot Burner Adjustment

The pilot flame should envelope approximately 3/8 to
1/2 inch of sensor tip (see Figure 23). To adjust pilot
flame:
a. Remove the pilot adjustment cover screw from the

gas control.

b. Turn pilot adjustment screw clockwise to decrease

or counterclockwise to increase pilot flame.

c. Replace pilot adjustment cover screw.

SAFETY CHECK

Removing Control Box (cover). See Figure 24.
To remove control box:
a. Turn black screw 1/4 turn clockwise to open position.

b. Remove two sheet metal screws in the top of control box.

c. Remove control box.
To replace the box, reverse procedure. Be sure that black
screw is in the lower bracket receptacle and lock position.

Boiler rated input in

cu. ft./hr. of 1000 Btu/cu. ft.

Natural Gas

30
60
90

120
150
180

Cubic Feet Gas Consumption

1000 Btu/cu. ft. gas, in

3 minutes, at rated input

1.50
3.00
4.50
6.00
7.50
9.00

Figure 22.

Figure 23.

Gas Rate Table