Sequence of operation for galaxy boilers – Slant/Fin GXH-190 User Manual

Page 20

Advertising
background image

20

GALAXY

SEQUENCE OF OPERATION FOR GALAXY BOILERS

HIGH-LIMIT CONTACTS CLOSED?

VENT DAMPER RELAY ENERGIZED.

VENT DAMPER MOTOR MOVES OPEN VENT DAMPER.

END SWITCH CLOSES.

IGNITION CONTROL ENERGIZED

SPARK GENERATOR MODULE POWERED

S8600F OR S8600M: IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS.

S8670E: IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30-70 SECONDS.

L.P. PROPANE GAS

(S8600M AND S8670E)

IGNITION TRIAL CONTIN-

UES FOR 90 SECONDS.

AFTER TRIAL FOR IGNI-

TION, SYSTEM SHUTS OFF.

AFTER 5 MINUTES MOD-

ULE RE-INSTATES TRIAL

FOR IGNITION. IF PILOT

FLAME NOT ESTABLISHED,

IGNITION TRIAL, SYSTEM

SHUT-OFF AND 5 MINUTES

WAIT SEQUENCE REPEATS

CONTINUOUSLY.

NATURAL GAS (S8600F)

IGNITION SPARK CON-

TINUES. PILOT VALVE

REMAINS OPEN UNTIL

SYSTEM IS RESET.

SPARK GENERATOR OFF. MAIN VALVE OPERATOR OPENS. MODULE MONITORS PILOT FLAME.

THERMOSTAT CALLS

FOR HEAT

CIRCULATOR IS OFF UNTIL

BOILER WATER TEMPERATURE

REACHES 120˚F

LOW LIMIT (FOR BOILERS WITH

TANKLESS COIL) CALLS

FOR HOT WATER

THE PILOT FLAME ESTABLISHED?

WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT, LOW LIMIT, OR LOW WATER CUT-OFF CONTACTS ARE OPEN,

VALVE OPERATORS CLOSE, VENT DAMPER CLOSES. CIRCULATOR OFF. SYSTEM GOES TO STANDBY.

NO FURTHER

ACTION

OR

NO

NO

NO

YES

YES