Sequence of operation for galaxy steam boilers – Slant/Fin GXHA-200 User Manual

Page 15

Advertising
background image

GALAXY STEAM BOILER

15

SEQUENCE OF OPERATION FOR GALAXY STEAM BOILERS

LOW WATER CUT-OFF CONTACTS CLOSED?

PRESSURE CUT-OUT CONTACTS CLOSED?

VENT DAMPER RELAY ENERGIZED.

VENT DAMPER MOTOR MOVES OPEN VENT DAMPER.

END SWITCH CLOSES.

IGNITION CONTROL ENERGIZED

SPARK GENERATOR MODULE POWERED

S8600F OR S8600M: IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS.

S8670E: IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30-70 SECONDS.

L.P. PROPANE GAS

(S8600M AND

S8670E) IGNITION

TRIAL CONTINUES
FOR 90 SECONDS.

AFTER TRIAL FOR

IGNITION, SYSTEM

SHUTS OFF. AFTER

5 MINUTES MODULE

RE-INSTATES TRIAL

FOR IGNITION. IF

PILOT FLAME NOT

ESTABLISHED, IGNI-

TION TRIAL, SYS-

TEM SHUT-OFF AND

5 MINUTES WAIT

SEQUENCE

REPEATS

CONTINUOUSLY.

NATURAL GAS

(S8600F) IGNI-

TION SPARK

CONTINUES.
PILOT VALVE

REMAINS OPEN

UNTIL SYSTEM

IS RESET.

SPARK GENERATOR OFF. MAIN VALVE OPERATOR OPENS. MODULE MONITORS PILOT FLAME.

THERMOSTAT CALLS

FOR HEAT

MODELS WITH

VENT DAMPERS

LOW LIMIT (FOR TANKLESS COIL)

CALLS FOR HOT WATER

THE PILOT FLAME ESTABLISHED?

WHEN THERMOSTAT IS SATISFIED OR WHEN LOW LIMIT, PRESSURE CUT-OUT, OR LOW WATER CUT-OFF CONTACTS ARE

OPEN, VALVE OPERATORS CLOSE, VENT DAMPER CLOSES. SYSTEM GOES TO STANDBY.

NO FURTHER

ACTION

OR

NO

NO

NO

YES

YES