INTREPID
BURNER DATA – BECKETT CF-375 BURNERS FOR PACKAGED BOILERS ONLY
(For knocked-down & boiler burner units see publication no. TR-42KB)
TR-60
CF-375
2.60
2.25
45˚ P
HAGO
135
10
3
1
TR-60
CF-375
2.85
2.25
45˚ P
HAGO
160
10
2
2
TR-70
CF-375
3.00
2.5
45˚ SS
HAGO
145
10
4
3
TR-70
CF-375
3.10
2.5
45˚ SS
HAGO
155
10
4
4
TR-70
CF-375
3.35
2.75
45˚ B
DELEVAN
148
10
4
5
Boiler
Model
Nozzles
Burner
Model
*
Firing Rate
(GPH)
Size
(GPH)
Angle &
Type
MFG
Oil Pump Pressure
Setting (PSIG)
Air Shutter
Setting
†
Air Band
Setting
Head
Setting
†
Air shutter and air band settings shown are approximate ONLY.
See START-UP page 8.
*
All burner models shown are single stage.