SAFETY BAR

Activation causes the gate to reverse for a programmable distance and stop. If
Max Retry Count is enabled, gate waits a programmable pause time, then retries.
The gate will retry up to twice before faulting out.

RADIO INPUT (TB6)

RADIO RECV

Convenience terminals provide power and contact connection for a radio
receiver. Activation is the same as OPEN.

WARNING (TB8)

WARNING OUT Relay contacts close depending on the programmed setting of the warning

relay.

MAG LOCK INPUT (TB4)

MAG LOCK

Relay contacts close when the gate is fully closed.

SLAVE I/O INPUT (TB1)

SLAVE I/O

Input/output terminals are used to control a second gate operator.

PHONE LINE (J9)

PHONE LINE

Terminals connect the telephone line to the gate operator.

ADJUSTMENTS

OVERLOAD

Factory-set pot protects the gate operator from excessive motor current.

(R72)

If MAX Retry is enabled, when the limit is exceeded, a closing gate reverses

a programmed distance and an opening gate stops, waits a programmed

pause time, then tries to resume. The gate will retry up to twice before

faulting

out.

NOTE: Gate may be more sensitive to drag in one direction than the other.

NOTE: For swing gate operation, controls are Right/Clockwise and Left/Counterclockwise.
REVERSE

Adjustable pot controls gate sensitivity to blockages by the instantaneous

SENSE

rise in motor current. If MaxRetry count is enabled, when the limit is

RIGHT (R69)

exceeded, a closing gate reverses a programmed distance and an opening

gate stops, waits a programmed pause time, then tries to resume. The gate

will retry up to twice before faulting out.

REVERSE

Adjustable pot controls gate sensitivity to blockages by the instantaneous

SENSE

rise in motor current. If MaxRetry count is enabled, when the limit is

LEFT (R160)

exceeded, a closing gate reverses a programmed distance and an opening

gate stops, waits a programmed pause time, then tries to resume. The gate

will retry up to twice before faulting out.

NOTE: LiftMaster gate operators have two reverse sense adjustments

(right/clockwise and left/counterclockwise) where other gate operators have
only one. This allows greater flexibility of installation. For instance, you can
install a gate on an incline and not worry about sacrificing downhill gate
sensitivity.

INRUSH

Adjustable pot controls the delay in sensitivity to reverse sense inputs.

(R203)

This delay in sensitivity prevents the initial motor inrush current from

causing a fault condition. The weight of the gate determines this setting.

CONNECTORS

LIMIT SWITCH (J4)

Connector for the left/right limit switch cable.

24 VAC (TB7)

Provides 24 VAC @ 200mA for powering accessories.

BATTERY I/O (J11)

Connector for use by the Power Fail Operation unit.

PWR INPUT (J1)

Connector for AC input power.

MOTOR POWER (J3) Connector for the motor cable.