Basic controller operation – Winco GM100 User Manual

Page 2

Advertising
background image

1

Basic Controller Operation

1) Manual Start

a. Place selector switch in the RUN position.
b. Controller will begin start sequence.

•

Preheat (if programmed).

•

Crank and fuel systems are energized.

•

Control will crank disconnect
automatically once the engine has
been started.


2) Manual Stop

a. Place selector switch in the OFF position.

•

Power to fuel solenoid will be turned
off.


3) Automatic Operation

a. Place selector switch in the AUTO position.
b. Close the “REMOTE START” circuit to ground

for engine start.

•

Preheat (if programmed).

•

Crank and Fuel energized.

•

Control will crank disconnect
automatically once the engine has
been started.

c. Open the “REMOTE START” circuit to stop the

engine.