4. Engine Start & Stop

4.1 The controller is manual and auto start capable.

4.1.1 Manual Operation

4.1.1.1 Turn the panel selector switch to RUN.

4.1.1.2 A message of “Starting Engine” will appear on the display.

4.1.1.3 The controller will engage the starter and fuel systems.

4.1.1.4 The controller automatically crank disconnects when the unit

detects 450 RPM from the engine’s speed sensor or 100+
VAC from the generator output.

4.1.1.5 To stop the engine, move the toggle switch back to the OFF

position.

4.1.1.6 Once the engine has started the controller will begin

monitoring and displaying the engine and generator
parameters.

4.1.1.7 If a fault occurs while the engine is running, the control panel

will open the run circuit to the engine’s fuel system.

4.1.1.8 To clear a fault, the panel selector switch must be cycled to the

OFF position.

4.1.2 Automatic Operation

4.1.2.1 Set the panel selector switch to AUTO.

4.1.2.2 A message of “Unit in Auto” will appear on the display.

4.1.2.3 Closing the remote start circuit to ground will initiate an engine

start sequence.

4.1.2.4 The controller has a cycle crank routine programmed for 5

crank attempts of 10 seconds each.

4.1.2.5 Opening the circuit will initiate an engine shutdown.

4.1.2.6 Note: Ground must be common to the engine battery negative

for reliable remote start signals.