Electrical connections, A caution, A warning – Carrier 58DRC User Manual

Page 3: 58drc counterflow gas-fired furnaces

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

58DRC

Counterflow Gas-Fired Furnaces

Fig. 6

Furnace, Plenum, and Base Installed

on a Combustible Floor

Electrical Connections
LINE-VOLTAGE WIRING
NOTE. For additional information, refer to Procedures
for Gas-Fired Furnaces (packaged with the equipment)

IMPORTANT: Before proceeding with the electrical

connections, make certain that voltage, frequency,
and phase correspond to that specified on the unit

rating plate. Also, be sure that the service provided
by the utility company is sufficient to handle the addi­

tional load imposed by this equipment.

A

CAUTION

Do not connect aluminum wire between disconnect

switch and furnace.

See Fig. 7 for wiring diagram showing the proper field

high- and low-voltage wiring Make all electrical connec­
tions in accordance with the National Electrical Code

ANSI/ NFPA 70-1984 and any local codes or ordinances

that might apply.

Use a separate fused branch electrical circuit for this

furnace. A disconnecting means must be located within
sight from, and readily accessible from the furnace. In

some areas, the unit door switch may qualify as the dis­
connecting means

A

WARNING

The furnace must be electrically grounded in accord­
ance with local codes, the National Electric Code,

ANSI/ NFPA 70-1984 Do not use gas piping as an
electrical ground.

If line voltage wiring to the unit is encased in a non-

metallic sheath, connect the incoming ground wire to the

grounding wire inside the furnace junction box. If

metallic conduit is used, it will serve as the ground.

LOW-VOLTAGE WIRING — Make field low-voltage

connections at the low-voltage terminal strip See

Fig 7.

NOTE: Use AWG no. 18 color-coded copper thermostat

wire for lengths up to 100 feet Above 100 ft, use AWG
no. 16 wire

IMPORTANT The thermostat heat anticipator

must be set to match the amp draw of the gas valve

and electrical components in the R-W circuit.

Accurate amp draw readings can be obtained at

thermostat subbase terminals R and W. Figure 8
illustrates an easy method for obtaining the actual
amp draw.

*Some thermostat subbases require a jumper wire between subbase terminals R and 4 for ---------------------------------------------------

proper operation in heating and cooling applications that use a single transformer

-----------

NOTE If any of the original wire as supplied must be replaced, use same typeor equivalent wire --------------------------------------------

Fig. 7 — Heating and Cooling Application Wiring Diagram

-Field Low-Voltage Wiring
■ Field High-Voltage Wiring

Factory Low-Voltage Wiring

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Bookj 1 |4

PC101

Catalog No 535-843

PrintedinUSA

Foi m 58DRC-1SI

Pg 3

7-85

Replaces New

Advertising