The minimum maintenance that should be performed

on this equipment is as follows.

1. Check and clean or replace air filter each month or as

required.

2. Check blower motor and wheel for cleanliness and

lubrication each heating and cooling season. Clean

and lubricate as necessary.

3. Check electrical connections for tightness and controls

for proper operation each heating season. Service as

necessary.

A WARNING

As with any mechanical equipment, personal injury

can result from sharp metal edges, etc.; therefore,

be careful when removing parts.

Air Filter — Each furnace accommodates 2 filters
which are installed above the furnace in the return-air
plenum. See Fig. 12.

To clean or replace the filters, proceed as follows;

1 Disconnect electrical power before removing access

panel.

2. Remove upper access panel.
3. Reach up behind top plate, tilt filters toward center of

return-air plenum, remove filters, and replace or clean

as needed.

4 Some furnaces are equipped with reusable, washable

filters.

a. Clean with tap water.

b. Rinse and let dry. No oiling or coating of filters is

required.

c. Reinstall filters with cross-hatch binding facing

blower.

Blower Motor and Wheel (Fig. 14) — Clean and

lubricate as follows;

1. Remove upper access panel.

2. Loosen screw in vent pipe enclosure front and remove

vent enclosure front by sliding forward (toward front

of unit).

3. Disconnect vent pipe at first joint above unit and

swing vent pipe assembly to the side, supported by
suitable means (block of wood, etc.).

4. Slide vent pipe upward through the rectangular open­

ing in top plate and remove vent pipe from furnace

5. Remove 4 screws in vent pipe enclosure back and

remove enclosure back by tilting top toward blower,

and sliding bottom toward front of furnace.

6. Disconnect electrical leads from right side of Molex

speed selector. Note location of wires for reassembly.

7. Remove screws holding blower assembly against

blower deck and slide blower assembly out of furnace.

8. Squeeze side tabs of Molex speed selector and pull

it from blower housing.

9. For units with motor capacitor, loosen screw in strap

holding capacitor to blower housing and slide capac­
itor from under strap.

Fig, 14 — Dual Blower with Left-Hand Housing

and Wheel Removed

10

.

I I .

12

Mark blower wheel, motor, and motor support in

relation to blower housing before disassembly, to

ensure proper reassembly.

Loosen setscrew holding blower wheel onto motor

shaft.

Remove bolts holding motor mount to blower

housing and slide motor and mount out of housing.

Some motors have a ground wire attached to blower
housing; disconnect it also.

13. Lubricate motor.

a. Remove dust caps or plugs from oil ports located

at each end of motor

b. Use good grade of SAE 20 nondetergent motor oil

and put 16 to 25 drops in each oil port

c. Allow time for total quantity of oil to be absorbed

by each bearing.

d. After oiling motor, be sure to wipe excess oil from

motor housing.

e. Replace dust caps or plugs on oil ports.

14 Remove blower wheel from housing

a. Mark blower wheel orientation and cutoff loca­

tion to ensure proper reassembly.

b. Remove screws holding cutoff plate and remove

cutoff plate from housing.

c. Lift blower wheel from housing through opening.

15. Clean blower wheel and motor by using vacuum with

soft brush attachment. Care must be exercised not
to disturb balance weights (clips) on blower wheel

vanes. Also do not drop or bend wheel, as balance
will be affected.

16. Reassemble blower by reversing procedures 14a-14c.

Be sure wheel is positioned for proper rotation.

17 Reassemble motor and blower by reversing pro­

cedures 8-12. If motor has ground wire, be sure it is
connected as before.

18. Reinstall blower assembly in furnace.
19. Reinstall vent enclosure back.

20. Reinstall vent pipe through opening in top plate,

secure to draft hood and connect remainder of vent

pipe assembly.

21 Reinstall vent enclosure front, and secure with screw.

22. Reinstall access panel