Carrier 50DPE014 User Manual

Installation, start-up and service instructions

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

50DPE014

50DP016,020

Single-Package Cooling Units

Installation, Start-Up and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS..............................

1

INSTALLATION .................................................. 1-10
Step 1 — Provide Unit Support ..........................

1

• ROOF CURB

• ALTERNATE UNIT SUPPORT

Step 2 — Rig and Place Unit...............................

1

• POSITIONING

• ROOF MOUNT

Step 3 — Field Fabricate Ductwork...................

6

Step 4 — Make Unit Duct Connections.............

6

Step 5 — Trap Condensate Drain .......................

6

Step

6

— Make Electrical Connections..............

7

• FIELD POWER SUPPLY

• FIELD CONTROL WIRING

Step 7 — Make Outdoor Air Inlet

Adjustments......................................................

7

• MANUAL OUTDOOR AIR DAMPER

• OPTIONAL ECONOMIZER

Step

8

— Install Outdoor Air Hood.................. 10

START-UP.......................................................... 10-13
SERVICE.............................................................14-16

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning equip­

ment can be hazardous due to system pressure and elec­

trical components. Only trained and qualified service

personnel should install, repair or service air conditioning

equipment.

Untrained personnel can perform basic maintenance

functions of cleaning coils and filters and replacing

filters. All other operations should be performed by

trained service personnel. When working on air condi­

tioning equipment, observe precautions in the literature,

tags and labels attached to the unit and other safety pre­

cautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations.

Have fire extinguishers available for all brazing
operations.

A

WARNING

Before performing service or maintenance operations

on unit, turn off main power switch to unit. Electrical

shock could cause personal injury.

INSTALLATION

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof

curb in accordance with instructions shipped with this

accessory. Accessory roof curb and information required

to field fabricate a roof curb are shown in Fig. 1 and 2.

Install insulation, cant strips, roofing and flashing as

shown. Ductwork can be installed to roof curb before unit.

is set in place. Curb should be level. Unit leveling toler­

ance is ± 1/16 in. per linear ft in any direction. This is

necessary to permit unit drain to function properly. Refer

to Accessory Roof Curb Installation Instructions for

additional information as required.
ALTERNATE UNIT SUPPORT — When the curb

cannot be used, support unit with sleepers using unit curb

support area. If sleepers cannot be used, support long

sides of unit with a minimum of 3 equally spaced 4-in. x

4-in. pads on each side.

Step 2 — Rig and Place Unit

— Inspect unit for

transportation damage. File any claim with transporta­

tion agency. Do not drop unit, keep upright. Use spreader

bars over unit to prevent sling or cable damage. Rollers

may be used to move unit aeross a roof. Level by using

unit frame as a reference; leveling toleranee is ± 1/16 in.

per linear ft in any direction. See Fig. 3 for additional

information. Unit weight is shown in Table 1.

Four lifting holes are provided in ends of unit base rails

as shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING — Provide clearance around and above

unit for airflow, safety and service access (Fig. 4).

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book|l l4

PC111

Catalog No 565-104

PrintedinUSA

Form 50DP-26SI

Pg 1

7-88

Replaces: 50DP-25S1