Table 4 — Air Quantity Limits

#

UNIT MODEL

MIN CFM

MAX CFM

50DPE014

3750

6250

50DP016

4500

7500*

50DP020

5400

9000

'Indoor Fan Max Watts = 3000

Indoor Air Fan

— Fan belts and pulleys are factory

installed. Belts are secured to pulleys with tape.

Remove tape and, if required, adjust as described in

Service, Indoor Air Fan Adjustment.

50DP020 has 2 non-adjustable pulleys. Pulley A is

installed in unit. Pulley B is shipped in cardboard box

taped to vestibule below main control box.

Outdoor Air Fans and Motors

are factory set. Refer

to Service, Outdoor Air Fan Adjustment as required.

Return Air Filters

— Check that correct filters are

installed in filter tracks. See Table 1. Do not operate unit

without return air filters.

Outdoor Air jnlet Screens

— Outdoor air inlet

screens must be in place before operating unit.

Economizer Section

— Remove filter access

panel. Check that outdoor air damper is closed and return

air damper is open.

Economizer operation and adjustment is described in

Start-Up, Economizer Operation; and Service, Econo­

mizer Adjustment, respectively.

Base Unit Operation

COOLING — Unit power on. System selector switch at

COOL; fan switch at AUTO.; thermostat at a setting

below room temperature.
50DPE014 and 50DP016 — Compressor starts unloaded

on elosure of No. 1 eontact in thermostat.

Additional rise in room temperature closes contact

No. 2 in thermostat which de-energizes the unloader coil.

Compressor is now fully loaded.

Check cooling effects at a setting below room tempera­

ture. Check unit charge. Refer to Service, Refrigerant

Charge.

Reset thermostat at a temperature above room tem­

perature. Compressor(s) will shut off.

50DPO20 — Upon a rise in room temperature, cooling

contact No. 1 in the thermostat closes, energizing the

first-stage cooling contactor and the indoor fan con-

taetor. The first-stage compressor, outdoor fan motor

and indoor fan motor start and run.

Upon a further rise in room temperature, cooling

contact No. 2 in the thermostat closes, energizing the

second-stage cooling contactor. The second-stage

compressor starts and runs.

To Shut Off Unit — Set system selector switch at OFF

position or reset thermostat above room temperature.

Units with Signal-LOC“ protection device shut down on

any safety trip and thermostat light comes on. Determine

reason for safety trip. Restart compressor(s) by resetting

circuit breaker at unit.

HEATING — Turn on main power to unit. Set system

selector switch at HEAT, fan switch at AUTO.; and

thermostat at a setting above room temperature. First

stage of electric heater elements are energized on closing

of heating contact No. 1 in thermostat. On a further fall

of room temperature, heater eontact No. 2 closes ener­

gizing second-stage eleetric heater elements.

To Shut Off Unit — Set system selector switch at OFF.

VENTILATION AIR CIRCULATION (Continuous

Fan) — Unit power on. System selector switch at OFF,

HEAT or COOL; fan switch set at ON. Indoor fan con-

taetor is energized through the switch on the thermostat,

and the indoor fan runs continuously.

AUTOMATIC CHANGEOVER (with Automatic

Changeover Thermostat) — System selector switch set

at AUTO. When temperature of conditioned space rises

to cooling selector lever setting, unit automatically

switches from heating mode to cooling mode. When tem­

perature of the eonditioned space falls to the heating

selector lever setting, unit automatically changes from

cooling mode to heating mode. The thermostat is inter­

locked so that cooling and heating systems do not operate

at the same time.

HEAD PRESSURE CONTROL — All units have fan

cycling thermostats which, at 55 F, shut off one outdoor

fan motor. This permits unit to operate down to 40 F

outdoor air temperature.

Economizer Operation

— If unit is equipped with

modulating outdoor air control (economizer), it should

operate as follows:

COOLING MODE — Indoor and outdoor fans and com­

pressor energize when there is a call for cooling and

enthalpy of outdoor air is above enthalpy eontrol setting.

The economizer damper moves to VENT position.

Indoor fan starts and economizer damper opens fully

on a first-stage call for cooling when enthalpy of outdoor

air is below the enthalpy control setting. Compressor

remains off.

Compressor is energized and mechanieal cooling

integrates with economizer cooling upon a second-

stage call for cooling. If outdoor air temperature falls

below 50 F, cooling lockout switch prevents compressor

from operating.

Economizer damper modulates when mixed air tem­

perature is below mixed air thermostat setting.

A freeze protection thermostat (FPT) is located on the

indoor coil. It detects ice buildup and turns off the

compressor, thus allowing the coil to clear. Onee ice

melts, the compressor can be re-energized.

HEATING MODE — Outdoor air damper stays at

VENT position while indoor air fan runs.
NOTE: If fan switch is at ON position, and room thermo­

stat is satisfied, damper goes to ventilation position.