Fig. 9 — burner flames – Carrier 48KHA User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Open air shutter very slowly until yellow tip just

disappears, then secure air shutter in place with
locking screw.

3. Repeat steps 1 and 2 for each burner.

After air shutter adjustments have been com­

pleted, observe that flames on each burner are light
blue and soft in appearance, and that flames are

same height along entire length of each burner. See
Fig. 9.

CARRYOVER

shutter

BURNER
(NAT)

FLAME

RADIATOR

SCREEN

LOW NOx

CARRYOVER

AIR

SHUTTER

MANIFOLD

STANDARD

Fig. 9 — Burner Flames

BLOWER HEAT-RELAY OPERATION — Heat­

ing relay (see Fig. 6 and unit wiring diagram) is
located in the control box and adjusts to permit
either longer or shorter OFF cycles. The ON cycle
automatically adjusts as OFF cycle changes. Adjust­
ing lever on relay is factory-set at center position to
provide optimum performance for most installa­
tions. On unusual installations, or where line voltage

is considerably above or below rated voltage, an
increase or decrease may be required for length of
time blower remains on. To increase blower opera­
tion time, move adjusting lever toward right-hand
position. To decrease blower operation time, move
lever toward left-hand position.

AIRFLOW AND TEMPERATURE RISE — The
heating section of each size of unit is designed and

approved for heating operation within temperature
rise range stamped on unit rating plate.

Table 5 shows approved temperature rise range

for each unit and air delivery (cfm) at various tem­
perature rises. Heating operation airflow must pro­
duce a temperature rise that falls within the

approved range. Refer to Cooling Section Start-Up
and Adjustments — Indoor Airflow and Airflow
Adjustments to adjust heating airflow when
required.

HEATING SEQUENCE OF OPERATION —
See Fig. 10.

Models

48KHA,KLA

have

an

intermittent

electric-spark ignition system without a standing
flame. When manual shutoff is opened, gas flows to
gas valve. On a call for heating by the thermostat,
unit terminal R makes to unit terminal W. Pilot
valve solenoid of gas valve and spark generator are
energized. Gas flows to pilot and the pilot is ignited
within 4 seconds. The flame sensor proves the
presence of pilot flame within 0.8 seconds after pilot
ignition. The internal switching of gas valve de­
energizes spark generator, energizes main valve
solenoid and energizes heating delay relay. Gas
flows to main burners and is ignited by pilot flame.
Contacts of heating relay close between 60 and 90
seconds after burners are ignited, and blower motor
starts. Heating cycle is now in normal operation.
Unit will continue operating in heating cycle until

Table 5 — Air Delivery (cfm) at Indicated Temperature

Rise and Rated Keating Input

MODEL 48-

HEATING

INPUT
(Btuh)

TEMPERATURE RISE (F)

35

37

39

41

43

45

47

49

51

53

55

57

59

61

63

65

67

69

71

73

75

KLA118

40,(Ю0

794

751

712

678

646

617

591

567

545

524

505

487

471

455

441

427

-

-

-

-

-

KLA124

40,000

794

751

712

678

646

617

591

567

545

-

-

-

-

-

-

-

-

-

-

-

-

KHA024

75,000

-

-

_ "]

1212

1158

1109

1063

1022

983

947

914

883

854

827

809

778

-

-

-

KLA130

40,000

617

591

567

545

524

505

487

471

455

-

-

-

-

-

-

-

KHA030

75,000

-

-

1271

1212

1158

1109

1063

1022

983

947

914

883

854

KLA036/136

60,000

1190

1126

1068

1016

969

926

887

850

817

786

758

731

706

683

-

-

-

-

-

-

-

KHA036/136

100,000

1984

1877

1781

1694

1615

1543

1478

1417

1362

1310

1263

1218

1177

1138

1102

1068

1036

100$

978

951

926

KHA036BF/CF

125,000

щщ

1930

1846

1771

1701

1638

1579

1523

1472

1423

1378

1336

1296

1258

1223

1189

1158

KLA042/142

60,000

926

887

850

817

786

758

731

706

683

661

641

622

604

587

571

556

KHA042

125,000

1930

1846

1771

1702

1638

1579

1523

1482

1423

1378

1326

1296

1258

1223

1189

-

KLA048/148

80,000

1235

1182

1134

1089

1048

1010

975

942

911

KHA048

125,000

WM

ш

1930

1846

1771

1702

1638

1579

1523

1472

1423

1378

1336

1296

-

-

-

-

KLA160

100,000

1543

1478

1417

1362

1310

1263

1218

1177

1138

1102

-

-

-

-

-

-

KHA060

150,000

Ä?:

4Шщ

2325

2226

2135

2051

1974

1902

1835

1773

1715

1660

1609

1561

1516

1493

1483

1395

L

NOTE: Shaded areas of the table fall below the approved temperature rise range of the unit Dashed areas
of the table faII beyond the air delivery capability of the unit within the operating voltage range for all voltage
options for each size unit

12