TROUBLESHOOTING CHART

Table 10 — Cooling Service Analysis Chart

"1

SYMPTOM

PROBABLE CAUSE

REMEDY

Compressor and con-
denser fan will not start

Power failure

Call power company.

Fuse blown or circuit breaker

tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor,

transformer, or control relay

Replace component

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not start
but condenser fan runs

Faulty wiring or loose connections
in compressor circuit

Check wiring and repair or replace.

Compressor motor burned out,
seized, or internal overload open

Determine cause. Replace compressor.

Defective run/start capacitor,

overload, start relay

Determine cause and replace.

One leg of 3-phase power dead

Determine cause.
Replace fuse or reset circuit breaker.

Compressor cycles (other
than normally satisfying
thermostat)

Refrigerant overcharge or
undercharge

Blow refrigerant, evacuate system, and recharge to
nameplate

Defective compressor

Determine cause, replace.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor,

overload, or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser fan motor or
capacitor

Replace

Restriction in refrigerant system

Locate restriction and remove

Compressor operates
continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Leaking valves in compressor

Replace compressor

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil

Refrigerant overcharged

Purge excess refrigerant.

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser air restricted or air
short-cycling

Determine cause and correct.

Head pressure too low

Low refrigerant charge

Check for leaks, repair, and recharge

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction

Excessive suction pressure

High heat load

Check for source and eliminate

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Purge excess refrigerant

Suction pressure too low

Dirty air filter

Replace filter.

Low refrigerant charge

Check for leaks, repair, and recharge

Metering device or low side
restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase air quantity. Check filter — replace if necessary

Temperature too low in condi­
tioned area

Reset thermostat.

Outdoor ambient below 55 F

Install accessory low-ambient kit.

Field-installed filter drier
restricted

Replace.

23