CHECKING AND ADJUSTING REFRIGER­
ANT CHARGE — Refrigerant system is fully
charged with R-22 refrigerant, tested and factory
sealed. For most applications, factory charge is the
correct amount for best performance; however, this
charge may require a slight adjustment to attain
rated performance.

NOTE: Adjustment of refrigerant charge is not re­
quired unless unit is suspected of not having proper

R-22 charge. For all applications, correct R-22

charge for best performance is charge that results in
a suction gas superheat of 5 F at compressor inlet
when unit is operating at ARI rating conditions of
95 F db outdoor and 80 F db/67 F wb indoor.

A superheat charging label is attached to outside

of compressor access door. Label includes a Field

Superheat Charging Table and a Required Suction-

Tube (F) temperature chart.

Table 7 is intended for use when minor unit charge

adjustments are required. For large adjustments,
evacuate unit and weigh in charge according to unit
rating plate. Use Table 7 to approximate charge if
ARI rating conditions cannot be obtained. Refer to
required airflow rates in Table 8. Charge unit with
outdoor fan operating only at high speed.

An

accurate

superheat-,

thermocouple-,

or

thermistor-type thermometer, a sling psychrometer
and a gage manifold are required when using super­
heat charging method for evaluating unit charge.

Do not use mercury or small dial-type thermometers

because they are not adequate for this type of
measurement.

Proceed as follows:

1. Remove caps from low- and high-pressure serv­

ice fittings. See Fig. 4 for location of entrance
for refrigerant pressure gage hoses.

2. Using hoses with valve core depressors, attach

low- and high-pressure gage hoses to low- and
high-pressure service fittings, respeetively.

3. Start unit in cooling mode and let unit run until

system pressures stabilize.

4. Measure and record the following:

a. Outdoor ambient-air temperature (F db).
b. Evaporator inlet-air temperature (F wb).
c.

Suction-tube temperature (F) at low-side

service fitting.

d. Suction (low-side) pressure (psig).

Using Field Superheat Charging Table, compare
outdoor-air temperature (F db) with evaporator
inlet-air temperature (F wb) to determine desired
system operating superheat temperature.

Using Required Suction-Tube (F) table, com­

pare desired superheat temperature with suction
Oow-side) operating pressure (psig) to determine
proper suction tube temperature.

5.

6

.

Table 7 — Refrigerant Charging Label

DESIRED SUPERHEAT TEMPERATURE (F)

(Measured @ Low-Side Service Port)

OUTDOOR

EVAPORATOR AIR INLET EWB (F)

EDB (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

10

13

16

19

21

24

27

30

33

36

38

41

70

7

10

13

16

19

21

24

27

30

33

36

39

75

6

9

12

15

18

21

24

28

31

34

37

80

5

8

12

15

18

21

25

28

31

35

85

__

8

11

15

19

22

26

30

33

90

5

9

13

16

20

24

27

31

95

6

10

14

18

22

25

29

100

__

8

12

15

20

23

27

105

5

9

13

17

22

26

110

6

11

15

,

20

25

115

-

-

-

-

8

14

18

23

NOTES:

1 DashedAreas: Do not attempttocharge system undertheseconditionsor

refrigerant slugging may occur

2 Add charge if actual superheat temperature is higher than chart value

and remove if lower Allow ±3F for tolerance

REQUIRED SUCTION-TUBE TEMPERATURE (F) vs.

DESIRED SUPERHEAT TEMPERATURE (F)

(Measured @ Low-Side Service Port)

DESIRED

SUPERHEAT

SUCTION OR LOW-SIDE PRESSURE (Psig)

AT SERVICE PORT

TEMP (F)

61.5

64.2

67.1

70

73

76

79.2

82.4

85.7

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

32

67

69

71

73

75

77

79

81

83

34

69

71

73

75

77

79

81

83

85

36

71

73

75

77

79

81

83

85

87

38

73

75

77

79

81

83

85

87

89

40

75

77

79

81

83

85

87

89

91

NOTE: Measure suction-tube temperature with an accurate superheat
thermocouple, or thermistor-type thermometer

7. Compare actual suction-tube temperature with

proper suction tube temperature. Using a toler­
ance of ±3 F, add refrigerant if actual tempera­
ture is more than 3 F higher than proper suction
tube temperature, or remove refrigerant if actual
temperature is more than 3 F lower than required
suction-tube temperature.

NOTE: If the problem causing inaccurate readings is
a refrigerant leak, see Unit Preparation, Refrig­
erant Leaks section of these instructions.