Remove control, blower and compressor eom-

partment access panels to locate all electrical con­
trols and wiring. Check all electrical connections for
tightness. Tighten all screw connections. If any
smoky or burned connections are noticed: dis­

assemble the connection, clean all parts, restrip wire
end and reassemble connection properly and

securely.

After inspecting electrical controls and wiring,

replace all panels. Start unit and observe at least one
complete heating cycle and one complete cooling
cycle to ensure proper operation. If discrepancies
are observed in either or both operating cycles, or if
a suspected malfunction has occurred, check each
electrical component with proper electrical instru­
mentation. Refer to unit wiring label when making
these checkouts.

NOTE; Refer to heating and/or cooling sequence of
operation in this publication as an aid in determining
proper control operation.

Refrigerant Circuit

— Annually inspect all refrig­

erant tubing connections and unit base for oil accu­
mulations. Presence of oil generally indicates a
refrigerant leak.

If oil is detected or if low-cooling performance is

suspected, leak-test all refrigerant tubing using an
electronic leak detector, halide torch, or liquid-soap
solution. If a refrigerant leak is detected, see Unit
Preparation — Refrigerant Leaks.

If no refrigerant leaks are found and low-cooling

performance is suspected, see Cooling Section Start-

Up and Adjustments — Checking and Adjusting
Refrigerant Charge section.

Gas Input

— Gas input does not require checking

unless improper heating performance is suspected.'

If a problem exists, refer to Heating Section Start-
Up and Adjustments section.

Evaporator Airflow

— Heating and/or cooling

airflow does not require checking unless improper
performance is suspected. If a problem exists, be
sure all supply- and return-air grilles are open and

free from obstructions, and air filter is clean. When

necessary, refer to Cooling Section Start-Up and

Adjustments Indoor Airflow and Airflow Adjust­
ments section to check system airflow.

Fig. 11 — Position of Electrode to Pilot