INDOOR AIRFLOW AND ADJUSTMENTS

Table 8 — Rated Cooling and Heating Airflows

Models 48KHA,KLA end-discharge units have

direct-drive blower motors. All motors are factory-
connected to deliver proper heating and cooling
airflows at normal external static pressures (except
for some 208-v applications).

Table 5 shows heating airflow at various tempera­

ture rises. Table 6 shows both heating and cooling
airflows at various external static pressures for

Models 48KHA,KLA direct-drive units. Refer to

these tables to determine airflow for system being
installed. See Table 8 for rated cooling and heating

airflows.

NOTE; Be sure all supply- and return-air grilles are
open, free from obstructions and adjusted properly.

MODEL 48-

COOLING

HEATING

Rated

Airflow

(cfm)*

ESP

(in.wg)

Rated

Airflow

(cfm)*

Maximum

ESP

(in.wg)*

KLA118310BE

630

0 10

505

0.30

KLA124310BE

800

0 10

505

0 30

KHA024310BF

800

0 10

947

0 30

KLA130310BE

1000

0 15

462

0 30

KHA030310BF

1000

0 15

947

0.30

KLA136310BE

1200

0 15

758

0 30

KLA036510CE

1200

0 15

758

0 65

KLA036610CE

1200

0 15

758

0.65

KHA136310BC

1200

0 15

1155

0 30

KHA036510CE

1200

0 15

1155

0 65

KHA036310BF

1200

0 15

1445

0 30

KHA036510CF

1200

0 15

1445

0 65

KLA142310BE

1400

0 15

695

0 30

KLA042510CE

1400

0 15

695

0 65

KHA042310BF

1400

0 15

1445

0 30

KHA042510CF

1400

0 15

1445

0 65

KLA148310BE

1600

0 20

925

0 30

KLA048510CE

1600

0 20

925

0 65

KLA048610CE

1600

0 20

925

0 65

KHA048310BF

1600

0 20

1445

0 30

KHA048510CF

1600

0 20

1445

0.65

KLA160310BE

2000

0 20

1155

0 30

KHA060310BF

2000

0 20

1735

0 30

ESP — External Static Pressure

*Rated in accordance with U S Government D.O.E test pro­

cedures and/or ARl Standard 210-81

NOTE: When operating the 208/230-volt, 3-phase
versions of Models 48KHA048 and 48KHA060 at
208 volts, lead connections of blower motor must
be changed as indicated on unit wiring label to
ensure proper airflow.

Heating and/or cooling airflow of 208/230-v

direct-drive blower motors can be changed by
changing the lead connections of blower motor.

Motor leads are color-coded as follows:

black — high speed
blue — medium speed
red — low speed

NOTE: Some direct-drive blower motors do not
have lead for medium speed. Factory connections
and available optional connections are shown in
Table 6.

For all units, motor lead connected to heat relay

determines heating speed and resulting airflow; and
motor lead connected to cooling relay determines
the cooling speed and resulting airflow. See unit
wiring label.

To change heating and/or cooling speed, connect

appropriate color-coded lead to appropriate relay.
Be sure to properly insulate any unused motor lead.

See Make Wiring Connections, Special Procedures

for 208-v Operation section for proper procedures to
insulate an unused electrical lead.

When installing a 208- or 230-v direct-drive unit

that is factory-connected for heating and cooling
speeds that are not the same, and same speed for
both heating and cooling is required for a particular

application, connect appropriate color-coded lead
to terminal 2 of cooling relay and connect a field-
supplied jumper between heat relay and terminal 2
of cooling relay. Be sure to properly insulate unused
motor lead(s).

17