Table 3 — Electrical Data (60 Hz)

MODEL

48-

SERIES

VOLTS-

PHASE

OPERATING

VOLTAGE*

COMPR

FLA

MCAt

MAX

AMPS

MAX FUSE

SIZE (Amps)t

MIN WIRE

SIZE (AWG)t

MAX

WIRE

Min

Max

RLA

LRA

IFM

OFM

(75C Copper)

LENGTHt

KLA118

310BE

208/230-1

197

253

8 7

49 0

1 2

1 0

13 1

10 9

20

14

76

KLA124

310BE

208/230-1

197

253

11 7

63 0

1 7

1 0

17 4

14 4

25

12

89

KHA024

310BF

208/230-1

197

253

11 7

63 0

3 0

1 0

18 7

15 7

25

12

82

KLA130

310BE

208/230-1

197

253

13 7

76.0

3.1

1.0

21.2

17.8

30

10

115

KHA030

310BF

208/230-1

197

253

13.7

76 0

2.9

1.0

21.0

17.6

30

10

116

KLA136

310BE

208/230-1

197

253

17 6

88 0

4 6

1 0

27 6

23 2

40

10

88

KLA036

510CE

208/230-3

187

253

11 5

65 1

4 7

1 0

20 1

17 2

25

10

137

KLA036

610CE

460-3

414

506

5 1

32 8

1 9

0 6

8 9

7.6

15

14

272

KHA136
KHA036

310BE
310BF

208/230-1

197

253

17 6

88 0

3 8

08

26 6

22 2

40

10

92

KHA036

510CE.CF

208/230-3

187

253

11.5

65.1

5.6

1.0

21.0

18.1

25

10

130

KLA142

310BE

208/230-1

197

253

23.9

95.4

4.1

0.8

34.8

28.8

50

8

113

KLA042

510CE

208/230-3

187

253

15 3

82.0

5.6

1.0

25.8

21.9

35

10

108

KHA042

310BF

208/230-1

197

253

23.9

95.4

3.9

0.8

34.6

28.6

50

8

114

KHA042

51 DCF

208/230-3

187

253

15.3

82.0

5.0

1.0

25.2

21.3

35

10

111

KLA148

310BE

208/230-1

197

253

23.7

116.0

4.5

1.9

36.1

30.1

50

8

108

KLA048

510CE

208/230-3

187

253

14 7

92 0

7 8

2 2

28 4

24 7

35

10

96

KLA048

610CE

460-3

414

506

70

46 0

3 3

1 2

13 3

11 5

20

14

180

KHA048

310BF

208/230-1

197

253

23 7

116.0

3.7

1.9

35.3

29.3

50

8

111

KHA048

510CF

208/230-3

187

253

14 7

92 0

5 8

2.2

26.4

22.7

35

10

104

KLA1 60

310BE

230-1

207

253

27 8

130 0

6 2

1 9

42 9

35 9

60

8

100

KHA060

310BF

230-1

207

253

27 8

130 0

6 5

1.9

43 2

36 2

60

8

99

AWG — American Wire Gage
FLA — Full Load Amps

IFM — Indoor Fan Motor
LRA “ Locked Rotor Amps
MCA — Maximum Circuit Ampacity
OFM — Outdoor Fan Motor
RLA — Rated Load Amps

‘Voltage limits between which the unit will operate satisfactorily
flf other than 75 C copper wire is used, determine size from unit ampacity and the National

Electrical code Voltage drop of wire must be less than 2% of unit rated voltage Maximum
wire length is for one way along the wiie path from unit to service panel

^Maximum dual element size

SINGLE-STAGE HEAT 6 COOL-

MANUAL CHANGEOVER

SINGLE-STAGE HEAT 8 COOL-

AUTOCHANGEOVER

JUMPER-1

CONTACTOR TERMINALS
(SEE UNIT WIRING LABEL)

3

G]

_J

3

o

LiJ

>-

CD

q

:

LOW-VOLTAGE
PIGTAIL LEADS

FIELD SPLICE^

-------- —■

--------- ♦OHM^ —

CONTROL BOX

HIGH-VOLTAGE
PIGTAIL LEAD

.POWER

SUPPLY

FIELD-SUPPLIED
DISCONNECT PER NEC

3-PHASE

UNITS ONLY

, Field Low-Voltage Wiring
, Field High-Voltage Wiring
. Factory Low-Voltage Wiring
. Factory High-Voltage Wiring

NOTE: For manual changeover applications, use thermostat part no HH01AD042 with
subbase part no HH93AZ042; or thermostat part no HH01AD040 with subbase part no.
HH93AZ040

For automatic changeover, use thermostat part no HH07AT174 with subbase part no

HH93AZ096; or thermostat part no HH10AD041 with subbase part no HH93AZ041

Fig. 8 — High- and Low-Voltage Connections