START-UP CHECKLIST

A. Preliminary Information

OUTDOOR: MODEL NO.

SERIAL NO.

INDOOR: AIR HANDLER MANUFACTURER .

MODEL NO. _________________

SERIAL NO.

ADDITIONAL ACCESSORIES.

B. Pre-Start-Up

OUTDOOR UNIT

IS THERE ANY SHIPPING DAMAGE? ,

IF SO, WHERE:____________________

(Y/N).

WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N)______________

CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)______________

HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)______________

HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?

(Y/N)______

ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?

(Y/N)______

HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?

(Y/N)_____

CONTROLS

ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING

CONNECTIONS MADE AND CHECKED? (Y/N)_____________

ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)

HAVE CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)

INDOOR UNIT

HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?

ARE PROPER AIR FILTERS IN PLACE? (Y/N)_____________

HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?

DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)______________

HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)______________

(Y/N) _

(Y/N)

PIPING

ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED? (Y/N)

HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, EVAPORATORS,

TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)____________

LOCATE, REPAIR, AND REPORT ANY LEAKS___________________________________________________________

HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N)________________

HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? (Y/N)______________

IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES?

(Y/N)______

AC

BC

CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS:

AB________ V

(AB -h AC + BC)/3 = AVERAGE VOLTAGE = ____________

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

_____

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = _

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

V

V