Table 3 — electrical data – Carrier 38AH024-034 User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 3 — Electrical Data

60 HERTZ

UNIT

COMPRESSOR

FAN MOTORSt

UNIT 38AH

Volts

Supplied*

MCA

MOCP

ICF

RLA

LRA

Qty

FLA

Hp

3 Ph, 60 Hz

Min

Max

(Fuse)

Ckt 1

Ckt 2

Cktl

Ckt 2

(ea)

500

208/230

187

254

100 8

125

408.4

39.3

39.3

198

198

2

6.2

024

200

380

342

418

61 8

80

193.8

24 0

24.0

93

93

2

39

1

600

460

414

508

50.3

60

204.2

196

196

99

99

2

3 1

too

575

518

632

42 1

50

168.4

15.7

157

79

79

2

3.4

500

208/230

187

254

110.5

150

468.4

43.6

43 6

228

228

2

62

028

200

380

342

418

67.2

90

215 8

26 4

26 4

104

104

2

39

1

600

460

414

508

55.9

70

234 2

22 1

22 1

114

114

2

3 1

100

575

518

632

47.1

60

188.8

19.7

19 7

91

91

2

3.4

500

208/230

187

254

135 5

175

506.4

43.6

63.6

228

266

2

62

034

200

380

342

418

77.0

110

256 8

26.4

34 3

104

145

2

39

1

600

460

414

508

65.8

90

340.2

22.1

30.0

114

120

2

3.1

100

575

518

632

53 3

70

193.8

17.9

22 9

91

36

2

34

50 HERTZ

UNIT 38AH

UNIT

COMPRESSOR

FAN MOTORSt

Volts

3 Ph, 50 Hz

Supplied*

MCA

MOCP
(Fuse)

ICF

RLA

LRA

Qty

FLA
(ea)

Hp

Min

Max

Ckt 1

Ckt 2

Ckt 1

Ckt 2

800

230

198

254

101 2

125

268.8

39.3

39.3

128

128

2

6.4

024

300

346

311

380

62.8

80

194.8

24 0

24.0

93

93

2

44

1

900

400

342

400

46.5

60

204 0

180

18.0

99

99

2

3.0

800

230

198

254

1109

150

298 8

43.6

43.6

143

143

2

64

028

300

346

311

380

68.2

90

216.8

26.4

26.4

104

104

2

44

1

900

400

342

400

55.7

70

234 0

22 1

22 1

114

114

2

30

800

230

198

254

135.9

175

355 8

43.6

63 6

143

200

2

6.4

034

300

346

311

380

78 1

110

257.8

26.4

34.3

104

145

2

4.4

1

900

400

342

400

65.1

90

240 0

22 1

30 0

114

120

2

30

LEGEND

FLA

— Full Load Amps

IGF — Maximum Instantaneous Current Flow during starting (the

point in the starting sequence where the sum of the LRA for
the starting compressor, plus the total RLA for all running com­
pressors, plus the total FLA for all running fan motors is
maximum)

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps (complies with National Electrical Code

[NEC], Section 430-24) (U.S.A Standard)

MOCP

— Maximum Overcurrent Protection

RLA

— Rated Load Amps

’Units are suitable for use on electrical systems where volt­

age supplied to unit terminals is not below or above listed
minimum and maximum limits

tAII fans are protected by a single circuit breaker.

UNBALANCED 3-PHASE SUPPLY VOLTAGE - Never
operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine
the percent voltage imbalance:

% Voltage Imbalance

— 100 max voltage deviation from average voltage

average voltage

Example: Supply voltage is 240-3-60.

AB = 243 V
BC =236

V

AC =238

V

Average Voltage =

243 -F236 -F238

Determine maximum deviation from average voltage:

(AB) 243 -239 =4

V

(BC) 239 -236 =3 V
(AC) 239 - 238 = 1 V

Maximum deviation is 4 v.

Determine percent voltage imbalance:

4

% Voltage Imbalance = 100 x

239

1

.

1

%

= 239

V

This amount of phase imbalance is satisfactory as it is

below the maximum allowable 2%.

IMPORTANT: Contact your local electric utility com­

pany immediately if the supply voltage phase imbal­

ance is more than 2%.