Table 1A — Physical Data — English

UNIT 38AH

024

028

034

Circuit 1

Circuit 2

Circuit 1

Circuit 2

Circuit 1

Circuit 2

OPERATING WEIGHT (lb)

With Alurninum-FIn Coil

1760

1820

1880

With Copper-Fin Coil

1923

1982

2097

COMPRESSOR

Reciprocating Semi-Hermetic

Type

06DH824

06DA824

06DH328

06DA328

06DH328

06DA537

Quantity Cylinders (ea)

6

6

6

6

6

6

Speed (rpm) — 60 Hz

1750

1750

1750

1750

1750

1750

- 50 Hz

1450

1450

1450

1450

1450

1450

Capacity Steps

(FIOP or Асу) - %

100

100

100

100

100

100

- %

66*

__

66*

66*

- %

33t

33t

33t

Unloader Setting (psig)

Factory Installed

— Load

76

76

76

— Unload

58

58

58

OIL CHARGE PER CIRCUIT (Pt)

10

REFRIGERANT, TYPE**

R-22

Shipping Charge (lb)

3

3

3

3

3

3

Operating Charge, Typical (lb)

20

20

20

20

25

25

CONDENSER FANS

Propeller Type — Direct Driven

Quantity...Dia (in.)

2.. 30

2

30

2. .30

Nominal Hp

1 0

1 0

1.0

Nominal Airflow (cfm)

16,700

16,700

15,700

Speed (rpm) — 60 Hz

1140

- 50 Hz

950

Watts (ea) - 50/60 Hz

1550

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fin

Rows...Fins/in.

2.. 19

2

19

3.. 17

Total Face Area (sq ft)

39 20

39 20

39.20

Storage Cap. (Ib)tt

37 7

37.7

56.6

CONTROLS

Pressurestat (psig)
High Pressure

Cutout

426 ± 7

Cut-in

320 ± 20

Low Pressure

Cutout

27 ± 3

Cut-in

44 ± 5

Oil Pressure

Manual Reset

Cutout (Diff)

60

Cut-in (Diff)

8.8

FAN CYCLING CONTROLS

No. 2 Fan:

Temp Close (F)

70 ± 3

Temp Open (F)

60 ± 3

PRESSURE RELIEF

Fusible Plug

Location

Liquid Line, Suction Line, Compressor

Temp (F)

210

CONNECTIONS (Sweat) (ea ckt)

Suction — in. OD

1%

Liquid — in. OD

%

LEGEND

Diff — Differential
FlOP — Factory-Installed Option
VAV — Variable Air Volume

'Standard unit — single suction pressure-actuated unioader on compressor no 1

tVAV FiOP — doubie eiectrically actuated unloaders on compressor no 1

"With 25 ft of interconnecting piping

ttCondenser 80% full of liquid R-22 at 120 F