Fig. 10 — pilot assembly, 58ed,pb horizontal gas-fired furnaces – Carrier 580PB User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

58ED,PB

Horizontal Gas-Fired Furnaces

14

15

With the pilot bracket removed from burners, rebend
the pilot tubing and thermocouple at the second bend
per Fig. 10. Make sure there are no kinks in tubing.
Connect the 1/4 in. diameter pilot gas tubing (and
the thermocouple, if equipped on standing pilot
models) to the gas valve. Be careful not to kink the

aluminum tubing.

16. Check the pilot position as shown in Fig. 9 and 10.
17. Standing pilot models only: Mount the pilot bracket

on the crossovers of the first 2 burners on the side of

manifold where valve is now mounted (Fig. 10).
Connect thermocouple and the 1/4 in. diameter
pilot gas tubing to gas valve This requires adjust­
ments to pilot tubing and thermocouple. It is ex­
tremely important not to kink either the thermo­
couple or aluminum tubing.

Insert the manifold tray back into the furnace and
slide the burners into the heat exchanger tubes. The
locking device will not engage unless the manifold
is in the correct position.
Lock the manifold in place (on electronic ignition
models, be sure the ignition cable or sensing lead
is not pinched under the burners).
Remove the junction box cover and disconnect the
motor leads.

21.

Remove junction box. See Fig. 11. On standing

pilot models, remove 2 hole plugs from back side

of furnace and then remove junction hox.

IMPORTANT; Pull junction box straight out

from furnace until fan and limit is clear of side
panel.

22.

Mount the junction box on the opposite side of

furnace. Ensure door switch is kept towards the
blower door when mounting junction box

18.

19.

20

EDGE OF PILOT HOOD TO BE FLUSH TO

NOTE; The fan and limit dial will be upside down
when junction box is properly reversed. This does

not affect the operation of fan and limit.

Remove the strain relief holding the motor wires,
route motor leads under blower, feed wires into back
of junction box and snap the strain relief into place.

Reconnect motor leads and replace junction box

cover.

Replace hole plugs in openings where fan and limit

and motor leads were

26. Remove the draft hood and draft hood support clip

23

24.

25

PILOT
TUBE

PILOT ASSEMBLY AS SHIPPED

FROM FACTORY

PILOT ASSEMBLY AFTER FIELD REVERSAL

PILOT LOCATION

Fig. 10 — Pilot Assembly

Manufacturer

reserves the right to discontinue,

or change at any time, specifications or designs without notice and without incurring obiigations.

Book|1 [4

PC101

Catalog No 535-834

Printed in U S A

Form 58ED.PB-1S1

Pg 12

6-85

Replaces: 58PB-1 SI

For replacement Items use Carrier Specitied Parts

Tab i6al8a

Advertising
This manual is related to the following products: