Carrier 58DHL User Manual

Installation, start-up and service instructions, 58dhl, Downflow/horizontal induced-combustion furnaces

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING A COOLING

58DHL

Downflow/Horizontal Induced-Combustion Furnaces

Installation, Start-Up and Service Instructions

Sizes 055-115

= ~ —

NOTE:

Remove the Energy Guide tag from the furnace

when the installation is complete.

NOTE:

This is a highly specialized piece of equipment.

Before beginning the installation, READ THESE

INSTRUCTIONS CAREFULLY AND COMPLETELY.

INTRODUCTION

Before installing the furnace, refer to “Procedure for

Induced-Combustion Furnaces” (packaged with the equip­

ment) for information concerning combustion, venting, pip­

ing, and other standard installation practices. Further refer­

ence is made to the current edition of the National Fuel Gas

Code NFPA No. 54, TIA-54-1984-1/ANSI Z223.1-1984,

Z223.la-1987 and American Gas Association.

The inducedrcombustion vent system of this furnace is

designed to operate at zero or negative pressure at the vent

connector outlet. This furnace, therefore, comphes with the

National Fuel Gas Code (NFPA No. 54, TIA-54-1984-1/

ANSI Z223.1-1984, Z223.1a-1987), Part 7.3.4.b. This furnace

is also Usted by A.G.A. for use with the type B1 gas vent, as

described in the National Fuel Gas Code, Part 7.4.2.

Each furnace is shipped from the factory completely assem­

bled with multispeed direct-drive blower and wired ready for

indoor heating installation. AU sizes featxire a blower con­

trol center with easy-to-read low-voltage terminal strip to

ensure proper connections.

Table 1—Clearances (In Inches)

Sizes

055

075 thru 115

DOWNFLOW (In Alcove or Closet)

Sides—Single-Wali Vent

1

0

Type-B1 Double-Wall Vent

0

0

Back

0

0

Top

1

1

Front*—Single-Wall Vent

6

6

Type-B1 Double-Wall Vent

3

3

Vent—Single-Wall

6

6

Type-BI Double Wall

1

1

HORIZONTAL (In Alcove)

Sidesf

1

0

Back

0

0

Top—Single-Wall Vent

1

1

Type-BI Double-Wall Vent

0

0

Front*

18

18

Vent—Single-Wall

6

6

Type-BI Double-Wall

1

1

HORIZONTAL (In Closet)

Sidest

1

1

Back

3

3

Top—Single-Wall Vent

2

2

Type-BI Double-Wall Vent

2

2

Front*—Single-Wall Vent

6

6

Type-BI Double-Wall Vent

3

3

Vent—Single-Wall

6

6

Type-BI Double-Wall

1

1

*Provide a 30-in. service clearance in front of thè furnace,
tindicates suppiy or return sides when furnace is in the horizontai posi­

tion.

Fig. 1—Downflow

Aæo33

?

iiilil

n

Fig. 2—Horizontai

A88034

The output capacity and any representations of efficiency

for this product are based on standard Department of

Energy test procedures. The installed operation may veiry,

depending on installation, weather, or other factors.

A CAUTION

Do not install furnace in a corrosive or contaminated

atmosphere. Make sure aU combustion and circulating

are requirements hsted in “Procedure for Induced-Com­

bustion Furnaces” are adhered to, in addition to all

local codes and ordinances.

Do not use this furnace during construction when adhe­

sives, sealers, and/or new carpets are being installed. If

the furnace is required during construction, use clean

outside air for combustion and ventilation. Compounds

of chlorine and flourine when burned with combustion

air form acids which will cause corrosion of the heat

exchangers and metal vent system. Some of these com­

pounds are: paneling and dry wall adhesives, paints,

thinners, masonry cleaning materials, and many other

solvents commonly used in the construction process.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book] 1

I

4

PC 101 Catalog No. 565-807

Printed In U.S.A.

Form 58DHL-1SI Pg 1

5-88

Replaces: New

Tab 16a 18a

Advertising