Start-up and adjustment standing pilot models, A warning, Electronic ignition models – Carrier 580PB User Manual

Page 13: 58ed,pb horizontal gas-fired furnaces

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

HEATING & COOLING

58ED,PB

Horizontal Gas-Fired Furnaces

27. Remove the flue box cover and flue box cover gasket

and remount them where the draft hood was located.

See Fig. 12. Do not glue gasket to cover plate.

28.

Replace the draft hood support clip and the draft

hood where the flue box cover plate was located.
NOTE; All controls, wiring, draft hood and the
AG A lighting instruction plates must be located
on the same side of the furnace as the automatic
main gas valve. Reattach all wires to gas valve and
check against wiring diagram.

29. Elect}onic ignition models only: Reattach all wires

to the gas valve and the ignition cable to the ignition
control.

Check all wiring against the wiring diagram. Fig.

6 and 7.

30. After the furnace components have been reversed,

return to Step 3, Assemble Furnace Draft Hood and
proceed with remainder of installation.

START-UP AND ADJUSTMENT

Standing Pilot Models

OPERATIONAL CHECKOUT — The automatic gas
valve controls the flow of gas to both the pilot and
main burners. The manual valve built into the automatic
valve body has 3 positions- OFF, PILOT, and ON.
SEQUENCE OF OPERATION — The furnace operates

automatically. It is controlled by a thermostat which is
set at the desired temperature. When indoor temperature

/ drops below this setting, the thermostat turns on the

system.

When the thermostat calls for heat, power from the

transformer energizes the main gas valve (the pilot must
be lit already) and gas flows through the valve to the
burners. The pilot flame lights the burners.

A heat sensing switch automatically energizes the

blower when heat buildup is sufficient. The air is moved
by the blower over the heating element, thus warming it,
and it goes through the ducts to room registers.

When the thermostat is satisfied, the circuit is broken,

de-energizing the main gas valve and stopping gas flow
to the main burners.

The blower continues to run until the heat in the heat

exchanger is removed and then the sensing switch shuts
off the blower.

All forced air furnaces are equipped with a high

temperature limit switch which prevents the furnace
from overheating. If the furnace overheats for any

reason, the high temperature limit opens, breaking the
circuit to the gas valve. The blower motor continues to

run. The main burners cycle on limit until the fault is
corrected.

A

WARNING

If overheating occurs, or if the gas supply fails to
shut off, shut off the manual gas valve to the furnace

before shutting off the electrical supply.

Electronic Ignition Models

OPERATIONAL CHECKOUT — The automatic gas
valve controls the flow of gas to both the pilot and main
burners. The manual valve built into the automatic valve
body has 2 positions: OFF and ON.
SEQUENCE OF OPERATION — The furnace operates
automatically. It is controlled by a thermostat which is
set at the desired temperature. When indoor temperature
drops below this setting, the thermostat turns on the
system.

When the thermostat calls for heat, power from the

transformer simultaneously energizes the pilot gas valve
(inside the main gas valve) and the spark igniter. After
the pilot flame is established, the electrode ceases to
spark and the flame sensing probe acts to energize the
main gas valve, permitting gas flow to the burners.

A heat sensing switch automatically energizes the

blower when heat buildup is sufficient. The air is moved
by the blower over the heating element, thus warming it,
and it goes through the ducts to room registers.

When the thermostat is satisfied, the circuit is broken,

de-energizing the main gas valve and stopping gas flow

to the pilot and main burners. The blower continues to
run until the heat in the heat exchanger is removed and
then the sensing switch shuts off the blower.

JUNCTION
BOX

Fig. 11 — Junction Box

(Model 58ED Shown)

FLUE BOX
COVER
(GASKET IS

UNDERNEATH)

Fig. 12 — Flue Box Cover

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

BookH 14

PC101

Catalog No 535-834

PrintedinUSA

Form 58ED,PB-1SI

Pg 13

6-85

Replaces: 58PB-1 SI